A 200A rated panelboard (load center) has wiring space on each side that measures 4 inches wide by 4 inches deep. The total length of the wiring space on each side is 36 inches. Three individual splices that each consists of two 4/0 AWG THHN/THWN insulated conductors are connected by split-bolt connectors are located on one side of the panelboard in the wiring space. Each split bolt connector is about 1.5625 square inches (2 cubic inches). Does the NEC permit these splices in the wiring space area of a panelboard? If they are, do they comply with the NEC requirements for splices in enclosures?

A) Yes, No
B) Yes, Yes
C) No, No
D) No, Yes

Answer: B

Explanation: In 312.8 the NEC prohibits the use of enclosures for switches or overcurrent devices as junction boxes, auxiliary gutters, or raceways for conductors that feed through or tap off to other switches or overcurrent devices, unless adequate space for this purpose is provided.

The conductors shall not fill the wiring space at any cross section to more than 40% of the cross-sectional area of the space, and the conductors, splices and taps shall not fill the wiring space at any cross section to more than 75% of the cross-sectional area of that space.

Calculation:
Step 1. Wiring space on both side is 36 inches long by 4 inches wide by 4 inches deep. Disregarding the 36 inch length for this calculation, it's 16 square inches at any cross-sectional area (4 in. x 4 in. = 16 sq. in.). Seventy-five percent of 16 is 12 square inches of useable space. Forty percent of 16 is 6.4 square inches.

Step 2. Calculate the square inch area of #4/0 AWG THHN/THWN insulated conductors, which, according to Chapter 9, Table 5, is 0.3237 square inches. The total area of the conductors for each splice would be 0.6474 square inches (2 x 0.3237 sq in. = 0.6474 sq in.). Add to that the area of a split bolt connector, which for two 4/0 AWG conductors is estimated to be 1.5625 square inches, for a total of 2.2099 square inches per splice. Therefore, the total for all three splices would be 6.6297 square inches.

Even if all three splices were made in a very tight area, according to this calculation, there's adequate space, because 6.6297 is approximately 41% full. Up to 75% full is permitted. Therefore, this example is Code-compliant.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states.

Find More Code Quizzes »


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues