Q. What is the maximum number of 12 AWG THHN insulated conductors permitted in a strut-type channel raceway that is 1˝ inches by 1˝ inches and of unlimited length? The channel location is defined as indoors and dry. The ambient temperature does not exceed 30°C. The raceway sections of this strut-type channel are joined with external joiners.
A) 54
B) 55
C) 34
D) 35
Answer: A
Explanation: The number of conductors permitted in a strut-type channel raceway shall not exceed the percentage fill noted in Table 384.22. When using external joiners, Table 384.22 permits a 40% fill. Therefore, for a 1˝ inch by 1˝ inch strut-type channel, the allowable fill according to Table 384.22 is 0.731 square inches.
From Chapter 9, Table 5, the approximate area of a 12 AWG THHN insulated conductor is 0.0133 square inches. 0.731 ÷ 0.0133 = 54.96. However, we must round down to 54, so as not to exceed the 40% fill requirement.
Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
Labeling tool
Feb 10, 2012 7:58 AM
Emergency lighting controls
Feb 9, 2012 8:40 AM
Cupertino Electric Sponsors Construction Industry Academic Competition
Feb 8, 2012 4:14 PM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.