Jul 17, 2008 2:49 PM, By Steven Owen

Q. When installing a hand-hole enclosure flush with the surface of the earth surrounding it, do you know how to properly ground the enclosure, including the cover? The enclosure is metallic. The dimension of the hand-hole enclosure is 24 inches wide by 24 inches long by 12 inches deep. The conductors installed in the hand hole are feeders. The feeders are 2/0 AWG THWN-2 conductors installed in Schedule 80 PVC, which are turned up into the enclosure. The equipment-grounding conductor for the circuit is based on the 175A overcurrent device protecting the feeder conductors. What is the appropriate Code section you should reference for this type of installation? What is the appropriate size equipment grounding conductor and equipment-bonding jumper, which will bond the cover, for this installation?

    1. Grounding is not required for enclosures that are smaller than 36 inches wide by 36 inches long by 18 inches deep. Therefore, there is no Code section to reference.
    2. Section 250.66. Minimum conductor size is 8 AWG.
    3. Sections 314.30(D), 250.96(A), 250.102(C), 250.122 and Table 250.122. Minimum size equipment-grounding conductor and equipment-bonding jumper is 6 AWG.
    4. Section 314.27, 250.92, 250.102(C), 250.122 and Table 250.122. Minimum size equipment grounding conductor and equipment-bonding jumper is 2/0 AWG.

Answer: C

As per 250.102(C), 250.122 and Table 250.122, the equipment-grounding conductor and the equipment-bonding jumper for this circuit should be based on the 175A overcurrent device protecting the feeder conductors. This yields a minimum size equipment-grounding conductor and equipment-bonding jumper of 6 AWG.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.

Find More Code Quizzes »

Want to use this article? Click here for options!




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 4, 2010 5:06 PM

Whats Wrong Here?

Jan 21, 2010 4:40 PM

What's Wrong Here?

Jan 7, 2010 12:47 PM

View all What's Wrong Here?

product of the week

Enclosures

February 8, 2010

Enclosures

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!



EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues