Jun 18, 2009 3:33 PM, By Steven Owen

When installing feeder conductors for a stage or set (per Art. 530), an issue arises regarding the size of the overcurrent protection devices for the feeder conductors. Here's the situation.

The building is used primarily for motion picture production. The feeder conductors from the substation to the stages are protected by overcurrent protective devices (OCPDs) that are located in the substation. The overcurrent devices are multi-pole units. The calculated load is 500A, continuous. The feeder conductors consist of 2 sets of 400kcmil per phase, THHN or THWN conductors (the dual insulation rating on the conductor) installed in parallel in two separate raceways. For the purposes of ampacity adjustment, the neutral conductor in this example is not considered to be current-carrying.

What is the minimum conductor size required for the feeder conductors, and what is the maximum size OCPD setting permitted per the above-referenced section of the Code?

    1. 4/0 AWG; 600A rating or setting of the OCPD.
    2. 300kcmil; 2,280A setting of the OCPD.
    3. 400kcmil; 800A rating or setting of the OCPD.
    4. 400kcmil; 2,680A setting of the OCPD.

Answer: D

As per 530.18(B), "In buildings used primarily for motion picture production, the feeders from the substations to the stages shall be protected by means of overcurrent devices (generally located in the substation) having a suitable ampere rating. The overcurrent devices shall be permitted to be multi-pole or single-pole gang operated. No pole shall be required in the neutral conductor. The overcurrent device setting for each feeder shall not exceed 400% of the ampacity of the feeder, as given in the applicable tables of Art. 310."

In our example, the calculation would go as follows:

If we follow the requirements of 215.2(A)(1), a 125% multiplier is required for the continuous load.
500A x 1.25 = 625A
625A ÷ 2 conductors per phase = 312.5A per conductor, per each individual phase.

From the 75°C column of Table 310.16 [also reference 110.14(C)], a 400kcmil conductor is rated 335A.
335A x 2 = 670A
670A x 400% = 2,680A
This is the maximum setting permitted for the OCPD. [Refer to 240.6(A) for fixed trip circuit breakers or fuses and 240.6(B and C) for adjustable trip settings.] Note: 2,680A is the maximum setting permitted per this section of the Code. Lower settings may be used.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.

Find More Code Quizzes »

Want to use this article? Click here for options!




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 4, 2010 5:06 PM

Whats Wrong Here?

Jan 21, 2010 4:40 PM

What's Wrong Here?

Jan 7, 2010 12:47 PM

View all What's Wrong Here?

product of the week

Enclosures

February 8, 2010

Enclosures

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!



EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues