Jun 8, 2004 8:39 AM, By Steven Owen

Q. According to 110.14(C) of the 2002 NEC, what would the maximum allowable ampacity be for a 250 kcmil THHN conductor that feeds a piece of equipment protected by a 250A inverse-time circuit breaker at the point where the conductor receives its supply?

The terminals at the equipment aren't marked with temperature ratings. The terminals at the circuit breaker are marked 75°C. (You'll need to determine the conductor temperature rating).

For the purposes of this question only, disregard the load being served. It's non-continuous and is properly protected by the 250A circuit breaker. The conductor is already sized properly for the load served. Our concern is the maximum allowable ampacity of the 250 kcmil THHN conductor, as connected in this circuit.

Note: In next issue's question, we'll add information related to the load requirements and the sizing of the overcurrent device and the conductor, including the temperature limitations at terminations.

A) 290A
B) 255A
C) 215A
D) 205A

Answer: B

Explanation: First go to Table 310.16. The ampacity of a 250 kcmil THHN conductor from the 90°C column under ordinary conditions (with no adjustments of any kind being made) is 290A.

A 1993 Code change to Section 110-14(c), Temperature Limitations at Terminations, requires that when determining the (allowable) ampacity of a conductor, “the temperature rating associated with the ampacity of a conductor shall be selected and coordinated so as not to exceed the lowest temperature rating of any connected termination, conductor or device. Conductors with temperature ratings higher than specified for terminations shall be permitted for ampacity adjustment, correction, or both.”

In the example above, this means that the 250 kcmil THHN conductor really is rated at 290A, per Table 310.16. The THHN conductor has a rating of 90° C (Table 310.13). The terminals at the circuit breaker are marked 75° C. The terminals at the equipment aren’t marked with temperature ratings. Section 110.14 (C)(1)(b)(2) permits a 75°C rating under specified conditions. Because the lowest rating is 75° C, the ampacity from the 75°C column of Table 310.16 shall not be exceeded. The ampacity from the 75°C column is 255A. That is the maximum value that this conductor could be used for in this question.

Note: Sec. 110.14(C) has been revised in four consecutive Code cycles (1993, 1996, 1999, and 2002) and will be again in 2005.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states.

Find More Code Quizzes »

Want to use this article? Click here for options!




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues