Code Quiz
In a surface metal raceway that measures 4 in. by 2 in., what is the maximum number of 12 AWG THHN, 600V insulated, single conductors, operating at 480V nominal permitted? The surface metal raceway is designed to contain a maximum of 255 conductors, and the thickness of the metal is 0.040 in. nominal.
- 60
- 120
- 255
- It is not permitted to install conductors operating at 300V or more in a surface metal raceway.
Answer: C
Assuming a 20% fill, the number of conductors allowed is calculated as follows:
- 4 in. x 2 in. = 8 sq. in. (total sq. in. area)
- 20% (fill allowed) x 8 = 1.6 sq. in. (maximum usable space allowed)
- 1.6 sq. in. ÷ 0.0133 (sq. in. area for a single 12 AWG THHN conductor from Chapter 9, Table 5) = 120 (maximum number of conductors allowed)
Reference NEC Secs. 386.10, 386.12, 386.22, and Table 5 in Chapter 9.
Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
Labeling tool
Feb 10, 2012 7:58 AM
Emergency lighting controls
Feb 9, 2012 8:40 AM
Cupertino Electric Sponsors Construction Industry Academic Competition
Feb 8, 2012 4:14 PM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.