Code Quiz
Mar 19, 2009 3:14 PM, By Steven Owen
When grounding network interface units containing protectors, network interface units with metallic enclosures, primary protectors, and the metallic members of the network-powered broadband communications cables that are intended to be grounded, which of the following requirements apply to the grounding conductor?
- The grounding conductor shall be insulated. The grounding conductor shall be copper or other corrosion-resistant conductive material, stranded or solid.
- The grounding conductor shall not be smaller than 14 AWG copper, and have a current-carrying capacity approximately equal to that of the grounded metallic members and protected conductors of the network-powered broadband communications cable. In addition, the grounding conductor shall not be required to exceed 6 AWG.
- The grounding conductor shall be as short a practicable, be run in a straight line, and be protected where exposed to physical damage.
- All of the above requirements apply.
Answer: D
Article 830 focuses on network-powered broadband communications systems. Part IV deals with the grounding methods used with these systems. Section 830.100(A) outlines the grounding conductor requirements noted above. All requirements noted in answers A, B, and C apply to these types of systems.
Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.
Want to use this article? Click here for options!
© 2010 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
Whats Wrong Here?Mar 11, 2010 12:54 PM |
|
What's Wrong Here?Feb 18, 2010 5:04 PM |
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































