Code Quiz

Mar 6, 2008 6:13 PM, By Steven Owen


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Q. What is the allowable ampacity of any one of the current-carrying 12 AWG THHN insulated conductors installed in a cellular concrete floor raceway with 29 other current-carrying 12 AWG THHN conductors and five equipment grounding conductors? Disregard the terminals in your calculations.

    1. 30A
    2. 20A
    3. 13.5A
    4. 11.25A

Answer: C

As per Table 310.16, 12 THHN is a 30A conductor at 30°C (86°F). As per 310.15(B)(2)(a) and Table 310.15(B)(2)(a), the adjustment factor for 30 current-carrying conductors is 45%. Therefore, the calculation is as follows: 30A x 0.45 = 13.5A.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Commenting terms of use blog comments powered by Disqus

Want to use this article? Click here for options!

product of the week

Fuel Cell

October 6, 2008 9:51 AM

American Power Conversion Fuel Cell

View all 2008 Products of the Week

Recent Comments




Arc Flash Conferences   Code Change Conferences

www.createyourcountdown.com

Professionals provide answers to your questions.


EC&M TV

Arlington Indoor InBox

Easy install makes Indoor InBox preferred for power & low voltage applications. Furniture and appliances stay close to the wall!...

Listen
"Sizing Gen-Sets: Facts, Hints, and Good Judgment"
Listen
Sponsored By:

Learn how HRG technology can mitigate and reduce the arc flash hazard; design considerations to remember when specifying and installing an HRG system.
On-Demand Webinar
- Sponsored by I-Gard

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues