Code Quiz

Feb 21, 2008 1:07 PM, By Steven Owen


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Q. On a 3-phase, 4-wire, 277V multi-wire lighting circuit, which is protected at 20A, there is debate as to the proper application of 210.4(B) and 240.15(B). The question is whether or not three single-pole circuit breakers with an identified handle tie are permitted to serve as both the disconnecting means and the overcurrent protective device for this circuit, or whether a multi-pole circuit breaker is required. What is the correct answer?

    1. Circuit breakers installed with identified handle ties are permitted to serve as both the disconnecting means and overcurrent protection as stated in this example.
    2. Circuit breakers may be installed with or without identified handle ties to serve as the overcurrent protective device only (not as the disconnecting means).
    3. A multi-pole circuit breaker may serve as both the disconnecting means and overcurrent protective device.
    4. All the above are correct answers.

Answer: D

As per 210.4(B), “Each multi-wire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.” This clearly states that simultaneous disconnection is required. 240.15(B) focuses on overcurrent protection and gives you the choice of using single-pole circuit breakers with or without identified handle ties or multi-pole circuit breakers.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues