When it comes to the placement of Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits, which one of the following statements meets Code requirements?
- Class 1, Class 2 and Class 3 circuits (in any combination) can occupy the same cable, enclosure, or raceway with other circuits as long as all circuit conductors have the same insulation rating.
- Two or more Class 2 circuits can occupy the same cable, enclosure, or raceway with other circuits.
- Two or more Class 3 circuits can occupy the same cable, enclosure, or raceway with other circuits.
- Class 2 circuits can occupy the same cable, enclosure, or raceway with Class 3 circuits.
Answer: D
As per 725.139, Class 2 and Class 3 remote-control, signaling, and power-limited circuits shall be permitted to occupy the same cable, enclosure, or raceway with other circuits as long as the circuits are Class 2 or Class 3.
Cables and conductors of Class 2 and Class 3 circuits shall not be placed in any cable, cable tray, compartment, enclosure, manhole, outlet box, device box, raceway, or similar fitting with conductors of electric light, power, Class 1, non-power-limited fire alarm circuits, and medium power network-powered broadband communications circuits unless permitted by 725.136(B) through (I).
Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.
Want to use this article? Click here for options!
© 2009 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Nov 5, 2009 11:50 AM |
|
What's Wrong Here?Oct 22, 2009 11:16 PM |
|
What's Wrong Here?Oct 8, 2009 3:32 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By: