Code Q&A
Dec 11, 2006 2:44 PM, By Mike Holt
Q. Can Table 310.15(B)(6) be used to size service conductors to a duplex, where there is no firewall separating the units?
A. No. Table 310.15(B)(6) only allows a reduced-size service and feeder conductors for individual dwelling units of one-family, two-family, and multi-family dwellings meeting the requirements of 310.15(B)(6). However, the main power feeder conductors to each dwelling unit can be sized using Table 310.15(B)(6).
Want to use this article? Click here for options!
© 2009 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Nov 5, 2009 11:50 AM |
|
What's Wrong Here?Oct 22, 2009 11:16 PM |
|
What's Wrong Here?Oct 8, 2009 3:32 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:






























