Code Q&A
Oct 11, 2006 1:55 PM, By Mike Holt
Q. If an outdoor generator has a disconnect, do I need an additional disconnect where the conductors enter the building?
A. Where an outdoor-housed generator is equipped with a readily accessible disconnecting means located within sight (Art. 100 -- within 50 ft) of the building or structure, an additional disconnecting means isn’t required on or at the building or structure for the generator feeder conductors that serve the building or structure [700.12(B)(6), 701.11(B)(5) and 702.11].
Want to use this article? Click here for options!
© 2009 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Nov 5, 2009 11:50 AM |
|
What's Wrong Here?Oct 22, 2009 11:16 PM |
|
What's Wrong Here?Oct 8, 2009 3:32 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:






























