Code Q&A
Oct 8, 2004 12:36 PM, By Mike Holt
Q. When does the NEC require a main breaker in a load center?
A. Each lighting and appliance branch-circuit panelboard must be protected on the supply side [408.16(A)]. The overcurrent protection device can be located within the panelboard, or the panelboard’s feeder overcurrent protection device could be used if its rating doesn't exceed the ampere rating of the panelboard [408.16(A) Ex.1].
Got a Code question for Mike? Send it to him at mike@mikeholt.com.
Want to use this article? Click here for options!
© 2010 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
|
Whats Wrong Here?Jan 21, 2010 4:40 PM |
|
What's Wrong Here?Jan 7, 2010 12:47 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































