Code Q&A
Aug 8, 2005 10:35 AM, By Mike Holt
Q. What size grounding electrode conductor is required for a 1,200A service supplied with three sets of 600 kcmil conductors per phase?
A. When not run to a ground rod, concrete-encased electrode, or ground ring, the grounding electrode conductor must be sized in accordance with Table 250.66. Because the equivalent area per phase equals 1,800 kcmil, the grounding electrode conductor is required to be 3/0 AWG.
Want to use this article? Click here for options!
© 2010 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
Whats Wrong Here?Mar 11, 2010 12:54 PM |
|
What's Wrong Here?Feb 18, 2010 5:04 PM |
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































