Q. A large number of satellite professionals ground the satellite system to the nearest available water hose bib. Does the NEC permit this installation practice?

A. No. The satellite mast (810.15) and discharge unit (ground block) [810.20(C)] must be grounded (actually bonded) in accordance with 810.20. The electrode that’s suitable for this purpose includes the nearest accessible [810.40(F)(1)]:

a. Building or structure grounding electrode system (250.50).
b. Interior metal water-piping system, within 5 feet from its point of entrance [250.52(A)(1)]. (see the Figure)
c. Accessible bonding means [250.94].
d. Metallic service raceway.
e. Service equipment enclosure.
f. Grounding electrode conductor or the grounding electrode conductor metal enclosure.

Grounding the lead-in antenna cables and the mast helps in preventing voltage surges from static discharge from reaching the inner conductor of the lead-in cable. Because the satellite sits outdoors, wind creates a static charge on the dish as well as the wire attached to it. This charge can build up on the dish and cable until it jumps across an air space, often through the electronics inside the LNBF or receiver. Grounding the coaxial cable and dish to the building grounding electrode system helps in dissipating this static charge.

Nothing can prevent damage from a direct lightning strike, but grounding these systems in accordance with the NEC with proper surge protection (not NEC required) can help reduce damage to satellite equipment as well as protect other related equipment from nearby lightning strikes.

Got a Code question for Mike? Send it to him at mike@mikeholt.com.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues