Q. Is it good practice to bond the lightning protection system to the building grounding electrode system?
A. The Code requires the lightning protection system, if provided on a premise, to be bonded to the building or structure grounding electrode system [250.106]. This bonding connection is designed to minimize the difference of potential between the lightning protection system and the electrical system, which should reduce arcing between metal parts within the building.