ECM Buyers' Guide
  

Stumped by the Code?

Dec 1, 2008 12:00 PM, By Mike Holt, NEC Consultant

All questions and answers are based on the 2008 NEC.

An area such as an employee break room with a sink and cord-and-plug-connected cooking appliance (microwave oven) is not considered a kitchen.

Q. Is GFCI protection required for receptacles above the counter of a break room in an office building?

A. If the break room has a sink and permanent provisions for food preparation and cooking [Art. 100 Kitchen], then all 125V, 15A, and 20A receptacles in the kitchen area must be GFCI protected [210.8(B)].

Q. If we are using self-grounding receptacles with MC cable and metal boxes, do we need to connect the equipment grounding conductor to the receptacle?

A. No. Receptacle yokes listed as self grounding are designed to establish the bonding path between the device yoke and a metal box via the two metal mounting screws [250.146(B)].

Q. Where does the NEC require removal of abandoned line voltage wiring?

A. The only time the NEC requires removal of abandoned line voltage circuit conductors is for cellular concrete floors [372.13], cellular metal floors [374.7], underfloor raceways [390.7], information technology equipment if not installed in a metal raceway [645.5(F)], and temporary wiring [590.3].

Q. How far above a residential garage floor do receptacles need to be located?

A. The Code does not require any specific height for equipment located in residential garages. Receptacles may be mounted as low or as high as you would like them to be.

Q. Do I need to use 20A duplex receptacles for a 20A circuit?

A. No, Table 210.21(B)(3) allows a 15A duplex receptacle on a 20A circuit.

Q. Does the NEC contain torque requirements for conductor terminations?

A. No, except for motor control circuit devices [430.9]. However, it does have a Fine Print Note in 110.14 that states, “Conductors must terminate in devices that have been properly tightened in accordance with the manufacturer's torque specifications included with equipment instructions. Failure to torque terminals can result in excessive heating of terminals or splicing devices (due to a loose connection), which can result in a fire because of a short circuit or ground fault. In addition, this is a violation of 110.3(B), which requires all equipment to be installed in accordance with listing or labeling instructions.”

Q. Can we put multiple Type NM cables through a single knockout?

A. Yes, you can put multiple Type NM cables through a single knockout but only if the termination fitting is listed for the purpose. Most termination fittings are only listed for a single cable connection, but there are some that are listed for two cables [110.3(B) and 312.5(C)].

Q. Can a panel be installed in a bathroom?

A. Maybe. Overcurrent devices must not be located in the bathrooms of dwelling units, or guest rooms or guest suites of hotels or motels [240.24(E)]. Also, the service disconnecting means must not be located in a bathroom, even in commercial or industrial facilities [230.70(A)(2)].

Q. If an appliance is cord and plug connected, is a disconnecting means required?

A. No, a plug and receptacle can serve as the disconnecting means for a cord-and-plug-connected appliance if the plug connection is accessible [422.33(A)].

Find More Code Q&As »

Want to use this article? Click here for options!




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

Area Takeoff Tools

March 22, 2010

Area takeoff tools

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues