All questions and answers are based on the 2008 NEC.

An area such as an employee break room with a sink and cord-and-plug-connected cooking appliance (microwave oven) is not considered a kitchen.

Q. Is GFCI protection required for receptacles above the counter of a break room in an office building?

A. If the break room has a sink and permanent provisions for food preparation and cooking [Art. 100 Kitchen], then all 125V, 15A, and 20A receptacles in the kitchen area must be GFCI protected [210.8(B)].

Q. If we are using self-grounding receptacles with MC cable and metal boxes, do we need to connect the equipment grounding conductor to the receptacle?

A. No. Receptacle yokes listed as self grounding are designed to establish the bonding path between the device yoke and a metal box via the two metal mounting screws [250.146(B)].

Q. Where does the NEC require removal of abandoned line voltage wiring?

A. The only time the NEC requires removal of abandoned line voltage circuit conductors is for cellular concrete floors [372.13], cellular metal floors [374.7], underfloor raceways [390.7], information technology equipment if not installed in a metal raceway [645.5(F)], and temporary wiring [590.3].

Q. How far above a residential garage floor do receptacles need to be located?

A. The Code does not require any specific height for equipment located in residential garages. Receptacles may be mounted as low or as high as you would like them to be.

Q. Do I need to use 20A duplex receptacles for a 20A circuit?

A. No, Table 210.21(B)(3) allows a 15A duplex receptacle on a 20A circuit.

Q. Does the NEC contain torque requirements for conductor terminations?

A. No, except for motor control circuit devices [430.9]. However, it does have a Fine Print Note in 110.14 that states, “Conductors must terminate in devices that have been properly tightened in accordance with the manufacturer's torque specifications included with equipment instructions. Failure to torque terminals can result in excessive heating of terminals or splicing devices (due to a loose connection), which can result in a fire because of a short circuit or ground fault. In addition, this is a violation of 110.3(B), which requires all equipment to be installed in accordance with listing or labeling instructions.”

Q. Can we put multiple Type NM cables through a single knockout?

A. Yes, you can put multiple Type NM cables through a single knockout but only if the termination fitting is listed for the purpose. Most termination fittings are only listed for a single cable connection, but there are some that are listed for two cables [110.3(B) and 312.5(C)].

Q. Can a panel be installed in a bathroom?

A. Maybe. Overcurrent devices must not be located in the bathrooms of dwelling units, or guest rooms or guest suites of hotels or motels [240.24(E)]. Also, the service disconnecting means must not be located in a bathroom, even in commercial or industrial facilities [230.70(A)(2)].

Q. If an appliance is cord and plug connected, is a disconnecting means required?

A. No, a plug and receptacle can serve as the disconnecting means for a cord-and-plug-connected appliance if the plug connection is accessible [422.33(A)].

Find More Code Q&As »


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues