Code Quandaries: Stumped by the Code? January 2012

Your most pressing National Electrical Code (NEC) questions

All questions and answers are based on the 2011 NEC.

Q. Are outdoor receptacles at a dwelling unit required to be tamper-resistant?

A. Yes. According to 406.12, all non-locking type 15A and 20A, 125V receptacles in the following areas of a dwelling unit [210.52] must be listed as tamper-resistant:

  • Wall space — 210.52(A)
  • Small-appliance circuit — 210.52(B)
  • Countertop space — 210.52(C)
  • Bathroom area — 210.52(D)
  • Outdoors — 210.52(E)
  • Laundry area — 210.52(F)
  • Garage and outbuildings — 210.52(G)
  • Hallways — 210.52(H)

An Exception to this rule notes that receptacles in the following locations aren’t required to be tamper-resistant:

  1. Receptacles located more than 5½ ft above the floor.
  2. Receptacles that are part of a luminaire or appliance.
  3. A receptacle located within dedicated space for an appliance that in normal use isn’t easily moved from one place to another.
  4. Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a).

Q. If you replace a 2-wire receptacle with no equipment grounding conductor with a GFCI, is an equipment grounding conductor required for the GFCI?

A. If no equipment grounding conductor exists in the outlet box for the receptacle, such as old 2-wire Type NM cable without an equipment grounding conductor, existing nongrounding-type receptacles can be replaced using one of the following [406.4(D)(2)], as shown in the Figure (click here to see Figure).

    a. Another nongrounding-type receptacle.

    b. A GFCI-type receptacle marked “No Equipment Ground.”

    c. A grounding-type receptacle, if GFCI protected and marked “GFCI Protected” and “No Equipment Ground.”

GFCI protection functions properly on a 2-wire circuit without an equipment grounding conductor because the circuit equipment grounding conductor serves no role in the operation of the GFCI-protection device. See the definition of “Ground-Fault Circuit Interrupter” for more information.

Caution: The permission to replace nongrounding-type receptacles with GFCI-protected grounding-type receptacles doesn’t apply to new receptacle outlets that extend from an existing outlet box that’s not connected to an equipment grounding conductor. Once you add a receptacle outlet (branch-circuit extension), the receptacle must be of the grounding type, and it must have its grounding terminal connected to an equipment grounding conductor of a type recognized in 250.118, in accordance with 250.130(C).

Q. Section 220.54 expresses electric clothes dryer loads in watts, and Table 220.55 provides wattage demands for ranges. Can watts be converted to VA for service calculations?

A. Yes. The feeder/service load for electric clothes dryers located in a dwelling unit must not be less than 5,000W (5,000VA), or the nameplate rating of the equipment if more than 5,000W (5,000VA). Kilovolt-amperes (kVA) are considered equivalent to kilowatts (kW) for loads calculated in this section [220.54].

When a building contains five or more dryers, it’s permissible to apply the demand factors listed in Table 220.54 to the total connected dryer load. A clothes dryer load isn’t required if the dwelling unit doesn’t have an electric clothes dryer circuit receptacle outlet.           

Find More Code Q&As »






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues