Stumped by the Code? October 2011

Your most pressing National Electrical Code (NEC) questions answered

All questions and answers are based on the 2011 NEC.

Q. When is the neutral considered to be a current-carrying conductor for the purposes of ampacity adjustment?

A. There are a couple of cases when the neutral is considered to be current carrying. According to 310.15(B)(5), these include:

  • The neutral conductor of a 3-wire circuit from a 4-wire, 3-phase, 120/208V or 277/480V wye-connected system is considered a current-carrying conductor for conductor ampacity adjustment of 310.15(B)(3)(a) [310.15(B)(5)(b)]. Note: When a 3-wire circuit is supplied from a 4-wire, 3-phase, 120/208V or 277/480V wye-connected system, the neutral conductor carries approximately the same current as the ungrounded conductors (click here to see Figure).
  • The neutral conductor of a 4-wire, 3-phase, 120/208V or 277/480V wye-connected system is considered a current-carrying conductor for conductor ampacity adjustment of 310.15(B)(3)(a) if more than 50% of the neutral load consists of nonlinear loads [310.15(B)(5)(c)]. Note: Nonlinear loads supplied by a 4-wire, 3-phase, 120/208V or 277/480V wye-connected system can produce unwanted and potentially hazardous odd triplen harmonic currents (3rd, 9th, 15th, and so on) that can add on the neutral conductor. To prevent fire or equipment damage from excessive harmonic neutral current, the designer should consider increasing the size of the neutral conductor or installing a separate neutral for each phase. See the Informational Notes in 210.4(A), 220.61, and 450.3 for more information.

The neutral conductor of a 3-wire, single-phase, 120/240V system, or 4-wire, 3-phase, 120/208V or 277/480V wye-connected system isn’t considered a current-carrying conductor for conductor ampacity adjustment of 310.15(B)(3)(a) [310.15(B)(5)(a)].

Q. What field labeling is required to identify circuits served by electrical equipment such as panelboards and motor control centers?

A. All circuits and circuit modifications must be legibly identified as to their clear, evident, and specific purpose. Spare positions that contain unused overcurrent devices must also be identified. Identification must include sufficient detail to allow each circuit to be distinguished from all others, and the identification must be on a circuit directory located on the face or inside of the door of the panelboard. See 110.22 [408.4(A)]. Circuit identification must not be based on transient conditions of occupancy, such as Steven’s or Brittney’s bedroom.

All switchboards and panelboards supplied by a feeder in other than one- or two-family dwellings must be marked as to the device or equipment where the power supply originates [408.4(B)].

Q. When are systems required to be grounded?

A. Systems operating below 50V aren’t required to be grounded or bonded in accordance with 250.30, unless the transformer’s primary supply is from [250.20(A)]:

  • A 277V or 480V system.
  • An ungrounded system.

For systems more than 50V, the following systems must be grounded (connected to the earth) [250.20(B)]:

  • Single-phase systems where the neutral conductor is used as a circuit conductor.
  • 3-phase, wye-connected systems where the neutral conductor is used as a circuit conductor.
  • 3-phase, high-leg delta-connected systems where the neutral conductor is used as a circuit conductor.             

Find More Code Q&As »






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues