Make sure you pay attention to wet and dry location definitions when installing type NM cable.

Q. When adjusting the ampacity of a conductor due to conductor bundling, do we use the 90°C column ampacity or the 75°C column ampacity as listed in Table 310.16 for THHN?

A. According to 110.14(C), conductors are to be sized to the lowest temperature rating of any terminal, device, or conductor of the circuit, in accordance with the equipment terminal temperature rating. However, conductors with insulation temperature ratings higher than the termination's temperature rating can be used for conductor ampacity adjustment, correction, or both.

This means conductor ampacity must be based on the conductor's insulation temperature rating listed in Table 310.16, as adjusted for ambient temperature correction factors, conductor bundling adjustment factors, or both. The location of conductors can influence their ampacity as well. For example, THHW is a 90°C conductor in a dry location, but it's a 75°C conductor in a wet location. THHN/THWN-2 is a 90°C conductor, in wet, dry, or damp locations [Table 310.13(A)].

Example: The ampacity of each 12 THHW conductor in a dry location is 30A, based on the values listed in the 90°C column of Table 310.16. If we bundle nine current-carrying 12 THHN conductors, the ampacity for each conductor (30A at 90°C, Table 310.16) needs to be adjusted by a 70% adjustment factor [Table 310.15(B)(2)(a)].

Adjusted conductor ampacity = 30A × 0.70 = 21A

If the conductors are installed in a wet location, the ampacity of 12 THHW conductors is 25A according to the 75°C column of Table 310.16 [Table 310.13(A)].

Adjusted conductor ampacity = 25A × 0.70 = 17.50A, 18A [220.5(B)]

Q. Can Type NM cable be installed in a raceway in a ground floor slab?

A. Maybe. Type NM cable is not permitted to be installed in a wet location [334.12(B)(4)] and according to the definition of a “Location, Wet” as contained in Art. 100, “a raceway in concrete slab that is in direct contact with the earth is considered a wet location.” So in this case, the answer is no, you're not permitted to install Type NM cable in the raceway (Figure).

However, if a plastic vapor barrier is installed between the earth and the concrete slab, then the concrete slab is not in direct contact with the earth and any raceway in a concrete slab is not located in a wet location. Under this condition, Type NM cable is permitted in the raceway.

Q. Does the NEC specify a particular color arrangement for 3-phase systems?

A. No, but electricians often use the following color system for power and lighting conductor identification:

120/240V, single-phase — black, red, and white

120/208V, 3-phase — black, red, blue, and white

120/240V, 3-phase — black, orange, blue, and white

277/480V, 3-phase — brown, orange, yellow, and gray; or brown, purple, yellow, and gray

Q. If the interior “guts” of a panel have overspray from acoustical spray, what do you do?

A. The panelboard (guts) must be replaced because the internal parts of electrical equipment must not be damaged or contaminated by foreign material, such as paint, plaster, cleaners, etc. [110.12(B)].

Q. What are the NEC requirements for installing panels in clothes closets?

A. Overcurrent devices must not be located near easily ignitable material, such as in clothes closets. According to Art. 100, a clothes closet is an uninhabitable room or space intended primarily for storage of garments and apparel.

Q. What are the separation requirements when installing signaling and communications cables in cable trays with Type MC and TC cables?

A. None. However, if the power conductors are installed as individual conductors, then a separation of 2 inches or a barrier is required, in accordance with:

  • Coaxial cables [820.133(A)(1)(b), Ex 1]

  • Class 2 and 3 cables [725.136(B) and 725.136(I)]

  • Communications cables [800.133(A)(2), Ex 1]

  • Fire alarm cables [760.136(G)]

  • Intrinsically safe systems cables [504.30(A)(2), Ex 1]

  • Radio and TV cables [810.18(B), Ex 1]

Q. Can I run Type NM cables in raceways in aboveground wet locations?

A. No, cables installed in raceways in aboveground wet locations must be listed for use in wet locations [300.9], and Type NM cable is not listed for use in a wet location [334.12(B)(4)].

Find More Code Q&As »






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues