Code Quandaries
Jan 1, 2005 12:00 PM, By Mike Holt, NEC Consultant
Stumped by the Code?
Q. Where should the high-leg conductor from a 120/240V, 3-phase, 4-wire delta-connected system be landed? My utility requires it to be in the right hand or “C” phase position at the meter.
A. The NEC requirements are as follows:
Fig. 1. The high-leg conductor has nicknames like “wild-leg,” “stinger-leg,” and “bastard-leg.”
Panelboards. Since 1975, panelboards supplied by a 3-phase, 4-wire delta-connected system must have the high-leg conductor (208V) terminate to the “B” (center) phase of a panelboard [408.3(E)] (Fig.1 at right).
An exception to 408.3(E) permits the high-leg conductor to terminate to the “C” phase when the meter is located in the same section of a switchboard or panelboard.
Fig. 2. The high-leg is identified by color to prevent misidentification.
Disconnects. The NEC doesn't specify the termination location for the high-leg conductor in switch equipment (Switches — Art. 404), but the generally accepted practice is to terminate this conductor to the “B” phase.
Warning: When replacing equipment in existing facilities that contain a high-leg conductor, care must be taken to ensure that the high-leg conductor is replaced in the original location. Prior to 1975, the high-leg conductor was required to terminate on the “C” phase. Failure to re-terminate the high-leg in accordance with the existing installation can result in 120V circuits inadvertently connected to the 208V high-leg, which can have disastrous results.
Identification. On a 3-phase, 4-wire delta-connected system, where the midpoint of one phase winding is grounded, the conductor with the higher phase voltage-to-ground (208V) must be durably and permanently marked by an orange outer finish or another effective means. Such identification must be placed at each point on the system where a connection is made if the grounded neutral conductor is present (110.15, 215.8, and 230.56) (Fig. 2 above).
The high-leg conductor is also called the wild-leg, stinger-leg, or bastard-leg.
Utility equipment: As I understand it, the ANSI standard for meter equipment requires the high-leg conductor (208V-to-neutral) to terminate on the “C” (right) phase of the meter enclosure. This is because the demand meter needs 120V, which it gets from the “B” phase.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
Whats Wrong Here?Mar 11, 2010 12:54 PM |
|
What's Wrong Here?Feb 18, 2010 5:04 PM |
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































