At EC&M , we know NEC issues are very important to our readers. That's why we've dedicated a monthly department to answering your latest Code questions and concerns. When you find yourself stumped by the Code, just e-mail your question to mike@mikeholt.com for future consideration in Code Quandaries.

Q. When installing an outdoor antenna, can I ground the antenna and lead-in cable to a new 8-ft grounding rod?

A. No. When you install a ground rod for a communications system, you must bond it with a No. 6 copper or larger, bare or insulated conductor to the grounding electrode system, at the building or structure served. You must bond telecommunications systems [Sec. 800-40(b)], antennas and lead-in cables [Sec. 810-21(f)], CATV [Sec. 820-40(b)], and network-powered broadband communications systems [Sec. 830-40(b)] to one of the following locations:

  • Building or structure grounding electrode system, as described in Sec. 250-50.

  • Interior metal water pipe meeting the requirements of Sec. 250-104(a). The limitation of 5 ft in Sec. 250-50 does not apply.

  • Metal service raceway.

  • Service equipment enclosure.

  • Building or structure grounding electrode conductor.

  • Metal enclosure housing the building or structure grounding electrode conductor.

  • Accessible bonding means, such as 6 in. of No. 6 copper conductor, connected to the service equipment or raceway [Sec. 250-92(b)].

Q. A 230V central air-conditioning unit specifies a maximum 45A fuse or HACR breaker, with a minimum circuit ampacity of 27.8A. Can I use No. 10 THHN with a 40A HACR breaker?

A. Yes. Conductors supplying a motor compressor with additional load(s) shall have an ampacity not less than 125% of the highest motor or motor-compressor rating in the group, plus the other loads (Sec. 440-33).

Example: A/C with the following loads: compressor 18.7A, OD motor 1.8A, ID motor 2.6A.

Conductor nameplate size = 18.7A x 1.25 + 1.8A + 2.6A = 27.8A.

The NEC permits the protective device to have a rating or setting not exceeding 175% of the largest motor compressor-rated load current, plus the other loads. Where the protection at 175% is not sufficient for the starting current of the motor, you can increase the protection rating to 225% of the largest motor compressor-rated load current, plus the other loads [Sec. 440-22(b)].

Example: A/C with the following loads: compressor 18.7A, OD motor 1.8A, ID motor 2.6A.

Protection nameplate size = 18.7A x 2.25 + 1.8A + 2.6A = 46.48A (next size down =45A).

Q. I'm installing a 1200A service (three sets of 600kcmil per phase). What is the largest grounding electrode conductor the NEC requires for this service?

A. Sec. 250-66 says the sizing of the grounding electrode conductor is based on the type of electrode used:

Ground rod/plate electrode [Sec. 250-66(a) ]. Where the grounding electrode conductor connects to a ground rod or plate electrode [Sec. 250-52(c)(d)], the Code does not require that portion of the conductor that is the sole connection to the grounding electrode to be larger than No. 6 copper wire.

Concrete-encased electrodes [Sec. 250-66(b) ]. Where the grounding electrode conductor connects to a concrete-encased electrode [Sec. 250-50(c)], the Code does not require that portion of the conductor that is the sole connection to the grounding electrode to be larger than No. 4 copper wire.

Ground rings [Sec. 250-66(c) ]. Where the grounding electrode conductor connects to a ground ring [Sec. 250-50(d)], the Code does not require that portion of the conductor that is the sole connection to the grounding electrode to be larger than the conductor used for the ground ring. Note: A ground ring must be bare copper not smaller than No. 2, but it's often sized much larger.

Other electrodes . Where the grounding electrode conductor connects to any other electrode [Sec. 250-50], the conductor shall not be less than given in Table 250-66.

Q. I'm terminating No. 14 THHN stranded wire to a circuit breaker. One of the electricians on the job said terminating stranded wire to a breaker was a Code violation and that the NEC requires a fork connector whenever we terminate stranded No. 14 or No. 12 wire. Is this true?

A. No. The Code lists circuit breakers, receptacles, switches, and other devices for the termination of stranded wire on terminal screws.

Copyright 2001 by Intertec Publishing Corporation, A PRIMEDIA Company. All rights reserved.

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues