May 1, 2000 12:00 PM, By Mike Holt, NEC Consultant

Here are the latest short answers to questions posted on our Web site. In our discussion, we will cover topics from Secs. 200-6(d), 210-4(d), 210-5(a), 215-8, 230-56, 250-122(c), 384-3(e) and Table 250-122 of the National Electrical Code (NEC).

Q. Does the NEC require you to color code phase conductors?

A. No. There is no NEC rule requiring color coding of phase conductors, however Sec. 210-4(d) states "where more than one nominal voltage system exists in a building, each ungrounded conductor of a multiwire branch circuit, where accessible, shall be identified by phase and system. This means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means and shall be permanently posted at each branch-circuit panelboard."

This rule applies primarily for commercial and industrial buildings that have 208Y/120V for receptacle circuits and 480Y/277V for lighting and other equipment loads.

If two system voltages are not present, then the NEC doesn't require identification of multiwire branch circuits.

Note: You must identify the high-leg conductor with the color "orange." (See Secs. 215-8 for feeders, 230-56 for service conductors, and 384-3(e) for switchboards or panelboards.) When you install two voltage systems in the same raceway (or enclosure), one system's neutral can be white or natural gray and the other system's neutral must be white with a readily distinguishable different color stripe (other than green), or identified with other effective means. [See Secs. 200-6(d) and 210-5(a).]

Q. Can I use a single equipment-grounding conductor for a nonmetallic raceway containing multiple circuits?

A. Yes. Sec. 250-122(c) covers this issue. When you install multiple circuits in the same raceway, you can use a single equipment-grounding conductor for all circuits. The single equipment-grounding conductor is sized to the largest overcurrent device protecting the conductors in the raceway, in accordance with Table 250-122.

Find More Code Q&As »




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues