Code Q&A
Nov 13, 2007 4:08 PM, By Mike Holt
Q. When a conduit leaves a Class I, Division 1 classified paint spray room and goes under the concrete floor into a cabinet in the motor control room that is non-classified, is one sealing fitting in the paint mix room sufficient, or is an additional sealing fitting required in the non-classified area as well?
A. A single conduit seal in the spray area is okay, as long as it is within 10 feet of the Class I, Division 1 location boundary. There must be no fitting, except a listed explosionproof reducer, between the seal fitting and the point at which the conduit leaves the Class I, Division 1 location [516.4(A) and 501.15(A)(4)].
Want to use this article? Click here for options!
© 2009 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Nov 5, 2009 11:50 AM |
|
What's Wrong Here?Oct 22, 2009 11:16 PM |
|
What's Wrong Here?Oct 8, 2009 3:32 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:






























