Code Q&A
Oct 25, 2006 11:51 AM, By Mike Holt
Q. Do I have to use bonding jumpers around listed reducing washers?
A. No. According to the UL Guide Information for Electrical Equipment (White Book), listed metal reducing washers are considered suitable for grounding. This information can be found in section QCRV (Outlet Bushings and Fittings) of the UL White Book.
Want to use this article? Click here for options!
© 2010 Penton Business Media, Inc.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
Whats Wrong Here?Mar 11, 2010 12:54 PM |
|
What's Wrong Here?Feb 18, 2010 5:04 PM |
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































