Code Q&A
Sep 24, 2009 1:08 PM, By Mike Holt
Q. What is the maximum length of raceway I can use where the conductor ampacity is not required to be adjusted for conductor bundling?
A. The conductor ampacity adjustment factors of Table 310.15(B)(2)(a) don’t apply to conductors installed in raceways not exceeding 24 in. in length [310.15(B)(2)(a), Exception No. 3].
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
|
Whats Wrong Here?Jan 21, 2010 4:40 PM |
|
What's Wrong Here?Jan 7, 2010 12:47 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































