Aug 27, 2007 10:33 AM, By Mike Holt


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Q. What is the minimum service drop clearance above a roof?

A. In general, overhead service conductors must maintain a minimum vertical clearance of 8 feet above the surface of a roof for a minimum distance of 3 feet in all directions from the edge of the roof [230.24(A)]. If the slope of the roof exceeds 4 inches for every 12 inches, 120/208V or 120/240V conductor clearances can be reduced to 3 feet over the roof [230.24(A) Ex 2].

If the service mast is used in a through-the-roof application, 120/208V or 120/240V conductor clearances can be reduced to 18 inches over the overhang portion of the roof [230.24(A) Ex 3]. There must not be more than 6 feet of service-drop conductors over the overhang portion of the roof and the service mast can’t be located more than 4 feet from the edge of the roof overhang measured horizontally.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues