Code Q&A
Aug 13, 2007 1:52 PM, By Mike Holt
Q. Can I use aluminum rigid metal conduit in a Class 1, Div. I hazardous (classified) location?
A. Yes. Section 501.10(A)(1) requires threaded rigid metal conduit (RMC) or threaded steel intermediate metal conduit (IMC). There is no mention in the NEC that the RMC be steel, so aluminum RMC is acceptable, as long as it’s suitable for the environment.
Acceptable Use Policy blog comments powered by Disqus
Want to use this article? Click here for options!
© 2009 Penton Media, Inc.


































