Code Q&A
Aug 6, 2009 11:46 PM, By Mike Holt
Q. Can we use EMT in a masonry wall, or must we use RMC?
A. Electrical metallic tubing (EMT), elbows, couplings, and fittings can be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the condition [358.10(B)]. According to the UL White Book (Category FJMX), "galvanized EMT installed in concrete on grade or above generally requires no supplementary corrosion protection." If the galvanized EMT is in a concrete slab below grade (such as a concrete floor of a basement), or emerges from concrete into earth, supplemental protection may be required.
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Nov 5, 2009 11:50 AM |
|
What's Wrong Here?Oct 22, 2009 11:16 PM |
|
What's Wrong Here?Oct 8, 2009 3:32 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:






























