Code Q&A
Jul 16, 2009 10:53 AM
By Mike Holt
Q. Can we install a 3-wire feeder (no equipment ground) to a pool house and bond the neutral and ground at the new panel?
A. No. To quickly clear a ground fault and remove dangerous voltage from metal parts, the building or structure disconnecting means must be connected to the circuit equipment grounding conductor of a type described in 250.118. The supply circuit equipment grounding conductor must be sized in accordance with 250.122, based on the rating of the overcurrent device. [250.32(B)]
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
|
Whats Wrong Here?Jan 21, 2010 4:40 PM |
|
What's Wrong Here?Jan 7, 2010 12:47 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email

































