Code Q&A
Q. What is the rule for adjusting the ampacity of conductors based on the number of conductors in the raceway?
A. Where the number of current-carrying conductors in a raceway or cable exceeds three — or where single conductors or multiconductor cables are installed without maintaining spacing for a continuous length longer than 24 in. — the allowable ampacity of each conductor, as listed in Table 310.16, must be adjusted in accordance with the adjustment factors contained in Table 310.15(B)(2)(a). Each current-carrying conductor of a paralleled set of conductors must be counted as a current-carrying conductor.
For example, if you wanted to know the ampacity of 10 THHN, where four current-carrying conductors are installed in a raceway or cable in a dry location, you would calculate it as follows:
Adjusted Ampacity = Table 310.16 Ampacity x Bundled Ampacity Adjustment Factor from Table 310.15(B)(2)(a)
Table 310.16 ampacity for 10 THHN is 40A at 90ºC. The bundled adjustment factor for four current-carrying conductors is 0.80.
Therefore, the adjusted ampacity would be:
Adjusted Ampacity = 40A x 0.80 = 32A
Latest Articles
EV charger tester
May 25, 2012 8:26 AM
CFL/LED dimmer
May 24, 2012 8:48 AM
Load bank
May 23, 2012 9:33 AM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.