Jan 25, 2006 3:33 PM, By Mike Holt
Q. What is the largest size transformer permitted to be mounted above a suspended ceiling used for environmental air?
A. Dry-type transformers, rated not more than 50 kVA, are permitted above suspended ceilings or in hollow spaces of buildings, if not permanently closed in by the structure [450.13(B)].