Q. How is the conductor ampacity for photovoltaic (PV) circuits calculated?

A. PV circuit conductors must be sized to the larger of 690.8(B)(2)(a) or 690.8(B)(2)(b).

Sizing according to 690.8(B)(2)(a):
PV circuit conductors must be sized to carry not less than 125% of 690.8(A) current before the application of conductor ampacity correction [310.15(B)(2)(a) and 310.15(B)(3)(c)] and adjustment [310.15(B)(3)(a)].

Example: What's the minimum PV source circuit conductor ampacity before the application of conductor correction or adjustment for a string having a short circuit current rating of 11.80A; assuming all terminals are rated 75°C (see Figure)?
Conductor ampacity = (module Isc × 1.25)* × 1.25
= (11.80A × 1.25)* × 1.25
= (14.75A)* × 1.25
= 18.44A
Conductor ampacity = 14 AWG rated 20A at 75ºC [Table 310.15(B)(16)]

*As per 690.8(A)(1), "the maximum current shall be the sum of parallel module rated short-circuit currents multiplied by 125%."

Conductors terminating on terminals rated 75°C are sized in accordance with the ampacities listed in the 75°C temperature column of Table 310.15(B)(16) [110.14(C)(1)(a)(3)].

Example: What's the minimum PV output circuit conductor ampacity, before the application of conductor correction or adjustment, supplied by two PV source circuits, each having a short-circuit current rating of 11.80A; assuming all terminals are rated 75°C?
Conductor ampacity = (module Isc × 1.25 × number of source circuits)** × 1.25
= (11.80A × 1.25 × 2 strings)** × 1.25
= 29.5A** × 1.25
= 36.88A
Conductor ampacity = 8 AWG rated 50A at 75ºC [Table 310.15(B)(16)]

**As per 690.8(A)(2), "the maximum current shall be the sum of parallel source circuit maximum currents as calculated in 690.8(A)(1)."

Sizing according to 690.8(B)(2)(b):
Circuit conductors must be sized to carry 100% of 690.8(A) current after the application of conductor ampacity correction [310.15(B)(2)(a) and 310.15(B)(3)(c)] and adjustment [310.15(B)(3)(a)]. When performing conductor ampacity correction and adjustment calculations, use the conductor ampacity listed in the 90°C column of Table 310.15(B)(16) for THWN-2 insulated conductors [310.15(B)].

Example: What's the PV source circuit conductor ampacity after temperature correction for two current-carrying size 12 THWN-2 conductors in a circular raceway on the roof, ambient temperature is 90°F with 60°F temperature added in accordance with Table 310.15(B)(3)(c), supplying modules having a nameplate Isc rating of 11.80A?
Conductor ampacity = Table 310.15(B)(16) Ampacity at 90°C Column x Temperature Correction Temperature correction = 0.58, Table 310.15(B)(2)(a) based on 150°F (ambient plus 60°F roof temperature adder)
Therefore, conductor ampacity = 30A x 0.58 = 17.40A, which has sufficient ampacity after correction and adjustment to supply 690.8(A)(1) calculated current of 14.75A (11.80A x 1.25).

Example: What's the PV output current ampacity after temperature correction for two current-carrying 8 size THWN-2 conductors in a circular raceway on the roof where the ambient temperature is 90°F supplied by two parallel PV source circuits, each having a Isc rating 11.80A?
Conductor ampacity = Table 310.15(B)(16) Ampacity at 90°C Column x Temperature Correction
Temperature correction = 0.58, Table 310.15(B)(2)(a) based on 150°F (ambient plus 60°F roof temperature adder)
Therefore, conductor ampacity = 55A x 0.58 [Tables 310.15(B)(2)(a) and 310.15(B)(3)(c)] = 31.90A, which has sufficient ampacity after correction and adjustment to supply 690.8(A)(2) calculated current of 29.5A (11.80A x 1.25 x 2).

Find More Code Q&As »






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues