Q. Is it legal to splice conductors in an "LB" fitting?

A. Splices are only permitted in conduit bodies that are marked by the manufacturer with their volume; and the maximum number of conductors permitted in a conduit body is limited in accordance with 314.16(B) [314.16(C)(2)]. Short-radius conduit bodies, such as capped elbows, handy ells, and service-entrance elbows must not contain any splices or taps [314.5].

Make sure you know when it's acceptable to make a splice in a conduit body.

Example: How many 12 AWG conductors can be spliced in a conduit body that has a capacity of 15 cu. in.? (Figure 314-16C2 01) The answer is 6 conductors (15 cu in. ÷ 2.25 cu in. = 6.67) [Table 314.16(B)]

Q. Can I install a panel in the clothes closet of a house if the working space of 110.26 is maintained?

A. No. Overcurrent devices are not permitted to be located near easily ignitable material, such as in clothes closets.

Q. How do you properly size a generator? Is there a standard somewhere that provides any guidance?

A. Prior to the 2008 NEC, the Code was silent on requiring any types of calculations for optional standby systems. New to the Code in the 2008 edition is 702.5(B)(2), which tells us that the optional standby power source must have adequate capacity to supply the full load transferred, if using an automatic transfer switch.

For a new installation, the load is determined by Art. 220 or an alternate method approved by the AHJ. For existing facilities, the maximum demand data for one yearr or the average power demand of a 15-min. period over a minimum of 30 days can be used to size the power source [220.87].

Non-NEC considerations: Consider the type of load and impedance of the generator; it’s typical to size a generator for UPS services at three times the expected load in order to have the generator impedance low enough so that harmonics is not a problem. The issue with harmonics is due to the alternator size and impedance and not the engine. A less expense approach to this problem is to have an oversized alternator attached to the same size engine or specify an alternator with a lower sub-transient reactance. Generator sizing is complicated, and becomes even more so, when motor loads are involved. As generator performance varies with manufacturer, it’s a good idea to consult the manufacturer and avoid manufacturers who cannot give you an answer.

Q. Does the Code address sharing a neutral for two conductors of the same phase?

A. Well, not really. Section 310.10 is the closest thing you will find, which says conductors must not be used where the operating temperature exceeds that designated for the type of insulated conductor involved. With that said, it would be legal to do this if the neutral was big enough.

Q. I was written up for having my NM cable in the same drilled stud hole as my doorbell wiring. I have been doing this for years. Have I been wrong all this time?

A. No, you haven't been doing it wrong. The section you were probably cited was 725.136(A), which states, "Class 2 and Class 3 circuit conductors and cables must not be placed in any enclosure, raceway, or cable with conductors of electric light, power, and Class 1 circuits." Notice that this rule applies to conductors of electric light and power, not cables of electric light and power.

Q. We typically put the refrigerator for a house on its own circuit, but do I have to do this for commercial as well? These are very small refrigerators, if it makes any difference.

A. There is nothing that requires a refrigerator to be on an individual branch circuit, either for residential or commercial applications.

Q. Does the Code specify a maximum length for a disposal cord?

A. Yes. A flexible cord is permitted for a waste disposal if the cord has a grounding-type attachment plug, the cord length is at least 18 in. and not longer than 3 ft, the waste disposal receptacle is located to avoid damage to the cord, and the waste disposal receptacle is accessible [422.16(B)(1)].

Find More Code Q&As »






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues