May 1, 2009 12:00 PM, By Mike Holt, NEC Consultant

Your most pressing National Electrical Code (NEC) questions answered. All questions and answers are based on the 2008 NEC.

All questions and answers are based on the 2008 NEC.

Sealing and wiring methods in classified locations are directly related to flashpoints of flammable liquids.

Q. How does the Code address diesel fuel dispensers as they relate to hazardous locations?

A. The hazardous Class I location requirements contained in Art. 514 only apply where a flammable liquid having a flash point below 100°F [Art. 100 Volatile Flammable Liquid] is stored, handled, or dispensed [514.3(B)]. The flash point of diesel fuel is 100°F or above; thus, the area involving diesel fuel is typically not a classified location. But if the conduit for the diesel dispenser passes through the Class I area around the gasoline dispenser, then the installation must comply with the sealing and wiring method requirements of Art. 501 ( Figure ).

Q. Can a receptacle be installed above a suspended ceiling?

A. Receptacles are permitted above a suspended ceiling, but a flexible cord is not [400.8(5)]. Why install a receptacle above a ceiling if the flexible cord is not permitted in this space? Because the receptacle can be used for portable tools, it just can't be used for cord-and-plug-connected equipment fastened in place, such as a projector.

Q. Can a 3-way switch be used as a generator transfer switch for a single circuit in a house?

A. Transfer equipment must be suitable for the intended use and designed/installed to prevent interconnection of the utility and generator supply [702.6]. According to the UL White Book (category QJQR), “snap switches have not been investigated for switching a load between two alternate sources of supply.” Therefore, 110.3(B) would prohibit using a 3-way switch for transfer equipment.

Q. Can a light fixture and its associated wiring be mounted to a tree?

A. Trees can be used to support luminaires [410.36(G)], but they must not be used to support overhead conductor spans [225.26].

Q. Where does the Code require removal of line voltage conductors and raceways that are no longer in use?

A. Abandoned line voltage conductors are only required to be removed in cellular concrete floor raceways [372.13], cellular metal floor raceways [374.7], underfloor raceways [390.7], and information technology equipment [640.5(F)].

Q. Can service conductors go directly to a transfer switch, without a disconnect upstream of the transfer switch?

A. Electrical equipment must not be connected to the supply side of the service disconnect enclosure, except for the equipment listed in 230.82, which does not include transfer switches. If the transfer switch is the service disconnect and is marked as “suitable for use as service equipment” [230.66], it can be used as the service disconnect, which complies with this rule.

Q. I am remodeling an existing commercial building that has Type NM cable installed above the suspended ceiling. With this in mind, can I also install new Type NM cable above the suspended ceiling?

A. Type NM cable isn't allowed to be exposed in dropped or suspended ceilings in other than one-family, two-family, and multifamily dwellings [334.12(A)(2)]. Although this was allowed in many buildings under previous Code editions, you must comply with this rule now that it is no longer permitted.

Copyright 2009 by Penton Business Media Inc. All rights reserved.

Find More Code Q&As »




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

Panelboard

March 8, 2010

Panelboard

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues