The load on the service grounded "neutral" conductor in a newly designed commercial office building (208/120V 3-phase, 4-wire system) is 475A. The loads being served are nonlinear. The ungrounded service entrance conductors were sized based a calculated ...

The load on the service grounded "neutral" conductor in a newly designed commercial office building (208/120V 3-phase, 4-wire system) is 475A. The loads being served are nonlinear. The ungrounded service entrance conductors were sized based a calculated load of 775A that took into account numerous 3-phase loads, such as air conditioning and heating, that have no neutral load. What is the demand load, if any, on the grounded "neutral" conductor of this system?

A) 775A, neutral has to be the same size as phase conductors
B) 392.5A, 70% demand on portion exceeding 200A
C) 475A, no reduction permitted when serving nonlinear loads
D) 406.25A, 75% demand on portion exceeding 200A

Answer: C)

Explanation: Art. 220 has been reorganized in the 2005 NEC. Sec. 220.61(C) doesn't allow a demand of 70% or any other value to be applied to any portion of the neutral load. The grounded “neutral” conductor shall be based on the 475A calculation.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.