Q. Where a surge arrester is installed on a circuit operating at less than 1,000V, it shall comply with all but which of the following?
- The rating of the surge arrester shall be equal to or greater than the maximum continuous phase-to-ground power frequency voltage available at the point of application.
- The surge arrester shall be identified for the application.
- Surge arresters shall be marked with short-circuit current rating and shall not be installed at a point on the system where the available fault current is in excess of that rating.
- Surge arresters shall not be installed on ungrounded systems, impedance grounded systems, or corner grounded delta systems unless listed specifically for use on these systems.
Answer: B
As per 280.4(A)(2), surge arresters installed on circuits of less than 1,000V shall be listed.