Code Quiz

June 12, 2006
When installing wiring from a fire pump controller to a fire pump motor, which of the following wiring methods is not permitted?

Q. When installing wiring from a fire pump controller to a fire pump motor, which of the following wiring methods is not permitted?

A) Liquidtight flexible nonmetallic conduit

B) Type MC cable with an impervious covering

C) Electrical metallic tubing (EMT)

D) Rigid metal conduit (RMC)

Answer: C

Explanation: As per 695.6(E), the only wiring method not permitted in this type of installation is EMT.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at [email protected].

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.