Code Quiz

Sept. 23, 2004
Imagine a metal junction box that is 32 inches x 32 inches x 6 inches with two 4-inch EMT raceways connected directly across from one another on opposite walls. Each 4-inch raceway contains three 250 kcmil conductors. An additional 2-inch EMT raceway, ...

Imagine a metal junction box that is 32 inches x 32 inches x 6 inches with two 4-inch EMT raceways connected directly across from one another on opposite walls. Each 4-inch raceway contains three 250 kcmil conductors. An additional 2-inch EMT raceway, which contains three 4/0 AWG XHHW conductors, is connected to the back wall of the junction box directly opposite the removable cover, and another 2-inch EMT raceway has been connected to the bottom of the enclosure for a tap to a piece of industrial equipment. The 4/0 AWG conductors, which pass through the junction box, are installed in the 2-inch raceways. What's the minimum dimension required between either of the 4-inch raceways (installed in a horizontal position) and the 2-inch raceway connected to the bottom of the enclosure (installed in a vertical position)? Note: No conductors are installed between either of the 4-inch raceways or either of the 2-inch raceways.

A) 32 inches
B) 24 inches
C) 4 inches
D) No requirement for this installation

Answer: D)

Explanation: The following sentence located directly beneath the Exception to 314.28(A)(2) is seldom read, but its content is still important: “The distance between raceways enclosing the same conductor shall not be less than 6 times the trade diameter of the larger raceway.” This applies to angle or U-pulls, and it could be applied to 2-inch raceways, but not those in the question posed. In this example there’s no angle pull between the 4-inch raceway(s) and the 2-inch raceway(s), so this requirement doesn’t apply as the question is written.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states.

About the Author

Steven Owen

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.