Code Q&A

Q. What are the NEC requirements for using electrical metallic tubing (EMT) to physically protect NM cable?























A. For one, a nonmetallic bushing or adapter must be installed at the point where the cable enters the raceway [300.15(C)]. In unfinished basements, the raceway and metal outlet boxes must be grounded (bonded) to an effective ground-fault current path in accordance with 250.148 [334.15(C)].