A change to 338.10 of the 2002 NEC
A change to 338.10 of the 2002 NEC is meant to clarify that when Type SE service-entrance cable is used for interior wiring it needs to comply with the installation requirements of Parts I and II for NM cable, but not the 60°C conductor ampacity limitations of 334.80. This change simply reverts the text back to the requirements contained in the 1996 NEC. It’s important to note that Type USE cable can't be used for interior wiring because it isn't listed for this application.
Now consider the following example calculation:
Sec. 424.3(B) requires the branch-circuit conductor for electric space heating equipment to have an ampacity of not less than 125% of the total heating load. A 10kW heater with a 3A blower motor must be wired with a conductor that has an ampacity of at least 56A (10,000W ÷ 240V + 3A). Therefore, it's acceptable to use 4 AWG NM cable or 6 AWG SE cable.
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
EV charger tester
May 25, 2012 8:26 AM
CFL/LED dimmer
May 24, 2012 8:48 AM
Load bank
May 23, 2012 9:33 AM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.