A change to 338.10 of the 2002 NEC
A change to 338.10 of the 2002 NEC is meant to clarify that when Type SE service-entrance cable is used for interior wiring it needs to comply with the installation requirements of Parts I and II for NM cable, but not the 60°C conductor ampacity limitations of 334.80. This change simply reverts the text back to the requirements contained in the 1996 NEC. It’s important to note that Type USE cable can't be used for interior wiring because it isn't listed for this application.
Now consider the following example calculation:
Sec. 424.3(B) requires the branch-circuit conductor for electric space heating equipment to have an ampacity of not less than 125% of the total heating load. A 10kW heater with a 3A blower motor must be wired with a conductor that has an ampacity of at least 56A (10,000W ÷ 240V + 3A). Therefore, it's acceptable to use 4 AWG NM cable or 6 AWG SE cable.
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
Labeling tool
Feb 10, 2012 7:58 AM
Emergency lighting controls
Feb 9, 2012 8:40 AM
Cupertino Electric Sponsors Construction Industry Academic Competition
Feb 8, 2012 4:14 PM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.