2011 National Electrical Code Changes

6. 250.30 Grounding Separately, Derived Systems

This section has been reorganized and includes many revisions and notes to clarify the grounding and bonding requirements of separately derived systems.

(A) Grounded Systems. Separately derived systems must be grounded and bonded in accordance with (A)(1) through (A)(8).

(3) System Neutral Conductor Size. If the system bonding jumper is installed at the disconnecting means instead of at the source, the following requirements apply:

(a) Sizing for Single Raceway. Because the neutral conductor of a derived system serves as the effective ground-fault current path for ground-fault current, it must be routed with the ungrounded conductors of the derived system and be sized not smaller than specified in Table 250.66, based on the area of the ungrounded conductor of the derived system. (click here to see Fig. 6)

(b) Parallel Conductors in Two or More Raceways. If the conductors from the derived system are installed in parallel in two or more raceways, the neutral conductor of the derived system in each raceway or cable must be sized not smaller than specified in Table 250.66, based on the area of the largest ungrounded conductor of the derived system in the raceway or cable. In no case is the neutral conductor of the derived system permitted to be smaller than 1/0 AWG [310.10(H)].

(6) Grounding Electrode Conductor, Multiple Separately Derived Systems.

(a) Common Grounding Electrode Conductor. The common grounding electrode conductor can be one of the following:

(1) A conductor not smaller than 3/0 AWG copper or 250kcmil aluminum.

(2) The metal frame of the building/structure that complies with 250.52(A)(2) or is connected to the grounding electrode system by a conductor not smaller than 3/0 AWG copper or 250kcmil aluminum.

(C) Outdoor Source. If the separately derived system is located outside the building/structure, a connection to the grounding electrode must be made at the separately derived system location.

Analysis: Considering the amount of changes that have occurred in this section, it wouldn’t be entirely inaccurate to say that the whole section has been rewritten. Here are a couple of items worth noting.

Section 250.30(A)(3) mainly borrows the text that was previously in 250.30(A)(8). It does, however, add new text to provide guidance on sizing the grounded conductor for a delta (corner grounded) system. In these applications, the grounded conductor must be the same size as the ungrounded conductors.

In 250.30(A)(6), the grounding electrode conductor(s) for multiple separately derived systems has been changed to clarify that structural metal can be used to ground multiple separately derived systems, provided that the structural metal complies with 250.52(A)(2) or is connected to the grounding electrode system by a conductor not smaller than 3/0 AWG CU or 250kcmil AL.

Section 250.30(C) is new to the NEC. This subsection addresses separately derived systems that are installed outside of a building or other structure. When this is the case, a grounding electrode connection to the transformer must be provided.

Discuss this Article 18

Anonymous (not verified)
on Sep 3, 2012

Why change the isolated ground receptacle requirement?the hospitals here have been @ for 40 years now.why did it take so long for the code makers to figure that out? Tr receptacles r too expensive to install,that means people will not hire electricians to replace there receptacles.they will install the traditional type or just not install new ones.I feel imbarrased about being an electrician because of these code rules.

Anonymous (not verified)
on Sep 3, 2012

I think the worst code change is having to add ur own support. To secure wire above a ceiling grid.shouldn't. U also have to support the luminaire as well.in fact,why not just use the support wires that support the grid. Most of the code changes are a waste of time and money.

Anonymous (not verified)
on Oct 25, 2012

Apparently you dont understand!

Anonymous (not verified)
on Sep 3, 2012

I just want to know why it took so long for them to come up with this stuff.we went to the moon in 69 and now they just figured out how to support wire above a ceiling!

Anonymous (not verified)
on Oct 17, 2012

The UL listing for a device that draws current should be what demands the neutral, not the NEC. Hundreds of millions of ordinary switch loops should not have to be saddled with the cost of the relatively few that need a neutral

Anonymous (not verified)
on Oct 26, 2012

Changes for conduit is it true no more 1/2" conduit can b used.

Anonymous (not verified)
on Oct 31, 2012

Can anyone tell me what code sections are applicable to roof mounted solar systems. Just the changes from 08-2011. What changes will have to be made to roof solar systems per 2011 that weren't applicable in 2008

Anonymous (not verified)
on Nov 2, 2012

Is there a code requirement for using a GCFI for sump pumps and/or ejectors in basements? Also is it required for clothes washers?

Anonymous (not verified)
on Nov 8, 2012

I heard of a new code stating each and every circuit has to have its own neutral ? no more A,B,C, phase with one nuetral "full Boat"? is this true?

Anonymous (not verified)
on Apr 5, 2013

you can still network if using handle ties or three pole breaker

Anonymous (not verified)
on Nov 8, 2012

AFCI not work properly in over 50%

Anonymous (not verified)
on Feb 4, 2013

The fire safety code requires the use of our own grid wires. To make sure lights don't fall out of the ceiling onto the fire fighters head. Sucks but makes sense. If you install a breaker lock on the circuits so they can be switched off at the same time, so there isnt any unbalanced neutral loads so you can work the circuit safely. Again common sense. Most of the code is written to protect people other than electricians.

Anonymous (not verified)
on Feb 19, 2013

Sounds like most people calling themselves "electricians " should probably take a code class to "refresh" what they should already learned about in apprentice class.

Anthony, IAEI Member (not verified)
on Feb 25, 2013

Anyone can become involved in the code change process. There are multiple organizations you can join. Every year thousands of people work hard to try and make the code as good as it can get, and every year we realize it’s not perfect. If you do not try and make a difference you have no right to complain. If you really want to try and make a difference join a group and get involved. Everyone acts like they have no control over these changes. If you sit on the sidelines all your life and just watch you will never be anything more than a spectator!

Anonymous (not verified)
on Mar 14, 2013

Codes are there for a reason.If anyone could understand and apply them properly electricians wouldn't make the $ we make.

Anonymous (not verified)
on Mar 15, 2013

If a home sustained water damages to the electrical box and flooded basement and all floors does the National Code require that all wiring to the entier house be replaced?

Anonymous (not verified)
on Mar 22, 2013

Yes. Any electrical equipment that has been flooded should be replaced.

NEMA has a great document guide for evaluating flood damaged electrical equipment. Here is the link.
http://www.nema.org/Standards/ComplimentaryDocuments/Evaluating-Water-da...

Anonymous (not verified)
on Apr 11, 2013

when do have to change from t12 tubes to t 5 for ballast

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Feb. 28, 2011
video
Electrical Construction and Maintenance

Arlington FBRS4200R

Arlington’s extra heavy-duty, plated steel fan/fixture box now has higher weight ratings…150 lbs for fixtures and 70 lbs for fans…when installed on joists spaced 16” on center…and 70 lbs for either a fan or fixture on joists spaced 24” on-center!...More

Newsletter Signup

Connect With Us