2011 National Electrical Code Changes

2. 210.8 GFCI Protection

There were several changes made to this section of the Code, addressing accessibility and location issues.

A new requirement addresses the accessibility of the test and reset functions of GFCI devices.

210.8 GFCI Protection. Ground-fault circuit interruption for personnel must be provided as required in 210.8(A) through (C). The Ground-fault circuit-interrupter device must be installed at a readily accessible location.

Analysis: The Code previously didn’t address the accessibility of the test and reset functions of GFCI devices. This presents two problems: First, building owners are subjected to the inconvenience of using ladders (or less safe devices) to reach the reset button should a GFCI device trip. Secondly, the listing standards of GFCIs require that they be tested on a monthly basis. While it’s true that many people don’t test their GFCI devices, some who would perform such tests won’t go through the extra effort of finding a ladder to access these devices if they aren’t readily accessible.

This change will require GFCIs in obvious locations, such as bathrooms and dwelling unit garages, to have their test and reset buttons readily accessible, but it also applies to less obvious locations, such as receptacles on rooftops and in soffits for holiday lighting.

A revision to this next requirement increases the locations of GFCI-protected outlets in patient care areas of health care facilities.

210.8(B)(5) Sinks. All 15A and 20A, 125V receptacles installed within 6 ft of the outside edge of a sink must be GFCI-protected.

Ex. 1: In industrial laboratories, receptacles used to supply equipment where removal of power would introduce a greater hazard aren’t required to be GFCI-protected.

Ex. 2: Receptacles located in patient bed locations of general care or critical care areas of health care facilities aren’t required to be GFCI-protected.

Analysis: A change to the 2008 NEC required GFCI protection near all sinks in nondwelling occupancies. One of the concerns raised by this change was the need for life support equipment to be supplied by an outlet that isn’t GFCI-protected. Due to this, an exception was written that exempted all receptacles in patient care areas (other than bathrooms). Although this certainly took care of the life support issue, it also removed GFCI protection from all other equipment that isn’t life safety oriented. For example, the many sinks found in a dental office were exempt, despite the fact that the patient is often very vulnerable to electric shock due to the invasive nature of many dental procedures. This change more accurately expresses the concerns of the medical community, while adding protection to equipment that isn’t essential to life support.

GFCI protection was added to indoor wet locations of nondwelling occupancies.

210.8(B)(6) Indoor wet locations. All 15A and 20A, 125V receptacles installed indoors in wet locations must be GFCI-protected.

Analysis: Many areas, such as car washes, food processing areas, and similar locations, share the same hazards as outdoor locations, yet GFCI protection has never been required in these locations. This change will now require that these areas receive the same protection against electric shock as required for outdoor locations. It’s worth noting that this change was accepted without any documented incidents cited.

A new requirement for GFCI protection of 15A and 20A, 125V receptacles near showering facilities was added.

210.8(B)(7) Locker Rooms. All 15A and 20A, 125V receptacles installed in locker rooms with associated showering facilities must be GFCI-protected.

Analysis: Requirements for GFCI protection of receptacles in bathrooms have been in place for a very long time. In Art. 100, a bathroom is very clearly defined — and not all locker rooms fall under that definition. The hazards that exist in a bathroom are the same as those encountered in a locker room — and perhaps even more so. A typical locker room that has associated showering facilities will probably contain tiled floors that are wet, people with bare feet, and people using electrical appliances (razors, hair dryers, curling irons, etc.). Therefore, GFCI protection was added for all 15A and 20A, 125V receptacles located in these facilities.

A new requirement adds GFCI protection for receptacles located in nondwelling unit garages that don’t fall under the scope of Article 511.

210.8(B)(8) Garages. All 15A and 20A, 125V receptacles installed in garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used must be GFCI-protected. (click here to see Fig. 2)

Analysis: This change expands GFCI protection requirements to all commercial garages. Article 511 applies only to those garages “in which volatile flammable liquids or flammable gases are used for fuel or power.” A facility that repairs only diesel-powered vehicles doesn’t fall under the requirements of Article 511, because diesel fuel is a combustible liquid, not a flammable liquid. Although the same electric shock hazards exist regardless of the fuel type employed, areas that use only diesel fuel didn’t require GFCI protection in previous editions of the Code.

Discuss this Article 18

Anonymous (not verified)
on Sep 3, 2012

Why change the isolated ground receptacle requirement?the hospitals here have been @ for 40 years now.why did it take so long for the code makers to figure that out? Tr receptacles r too expensive to install,that means people will not hire electricians to replace there receptacles.they will install the traditional type or just not install new ones.I feel imbarrased about being an electrician because of these code rules.

Anonymous (not verified)
on Sep 3, 2012

I think the worst code change is having to add ur own support. To secure wire above a ceiling grid.shouldn't. U also have to support the luminaire as well.in fact,why not just use the support wires that support the grid. Most of the code changes are a waste of time and money.

Anonymous (not verified)
on Oct 25, 2012

Apparently you dont understand!

Anonymous (not verified)
on Sep 3, 2012

I just want to know why it took so long for them to come up with this stuff.we went to the moon in 69 and now they just figured out how to support wire above a ceiling!

Anonymous (not verified)
on Oct 17, 2012

The UL listing for a device that draws current should be what demands the neutral, not the NEC. Hundreds of millions of ordinary switch loops should not have to be saddled with the cost of the relatively few that need a neutral

Anonymous (not verified)
on Oct 26, 2012

Changes for conduit is it true no more 1/2" conduit can b used.

Anonymous (not verified)
on Oct 31, 2012

Can anyone tell me what code sections are applicable to roof mounted solar systems. Just the changes from 08-2011. What changes will have to be made to roof solar systems per 2011 that weren't applicable in 2008

Anonymous (not verified)
on Nov 2, 2012

Is there a code requirement for using a GCFI for sump pumps and/or ejectors in basements? Also is it required for clothes washers?

Anonymous (not verified)
on Nov 8, 2012

I heard of a new code stating each and every circuit has to have its own neutral ? no more A,B,C, phase with one nuetral "full Boat"? is this true?

Anonymous (not verified)
on Apr 5, 2013

you can still network if using handle ties or three pole breaker

Anonymous (not verified)
on Nov 8, 2012

AFCI not work properly in over 50%

Anonymous (not verified)
on Feb 4, 2013

The fire safety code requires the use of our own grid wires. To make sure lights don't fall out of the ceiling onto the fire fighters head. Sucks but makes sense. If you install a breaker lock on the circuits so they can be switched off at the same time, so there isnt any unbalanced neutral loads so you can work the circuit safely. Again common sense. Most of the code is written to protect people other than electricians.

Anonymous (not verified)
on Feb 19, 2013

Sounds like most people calling themselves "electricians " should probably take a code class to "refresh" what they should already learned about in apprentice class.

Anthony, IAEI Member (not verified)
on Feb 25, 2013

Anyone can become involved in the code change process. There are multiple organizations you can join. Every year thousands of people work hard to try and make the code as good as it can get, and every year we realize it’s not perfect. If you do not try and make a difference you have no right to complain. If you really want to try and make a difference join a group and get involved. Everyone acts like they have no control over these changes. If you sit on the sidelines all your life and just watch you will never be anything more than a spectator!

Anonymous (not verified)
on Mar 14, 2013

Codes are there for a reason.If anyone could understand and apply them properly electricians wouldn't make the $ we make.

Anonymous (not verified)
on Mar 15, 2013

If a home sustained water damages to the electrical box and flooded basement and all floors does the National Code require that all wiring to the entier house be replaced?

Anonymous (not verified)
on Mar 22, 2013

Yes. Any electrical equipment that has been flooded should be replaced.

NEMA has a great document guide for evaluating flood damaged electrical equipment. Here is the link.
http://www.nema.org/Standards/ComplimentaryDocuments/Evaluating-Water-da...

Anonymous (not verified)
on Apr 11, 2013

when do have to change from t12 tubes to t 5 for ballast

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Oct. 17, 2012
video

MENNEKES ® AMAXX Easy One-man Installation

This video demonstrates the easy, one-man installation of an MENNEKES ® AMAXX unit. See how these custom power distribution units can save you time, money and space....More

Newsletter Signup

Connect With Us