What is in this article?:
- 2011 National Electrical Code Changes
- 1. 110.24 Available Fault Current
- 2. 210.8 GFCI Protection
- 3. 210.12 Arc-Fault Circuit-Interrupter Protection for Dwelling Units
- 4. 210.52 Dwelling Unit Receptacle Outlet Requirements
- 5. 250.2 Bonding Jumper, Supply-Side
- 6. 250.30 Grounding Separately, Derived Systems
- 7. 250.52(A) Electrodes Permitted for Grounding
- 8. 250.53(A) Rod, Pipe, and Plate Electrodes
- 9. 250.121 Use of Equipment Grounding Conductors
- 10. 300.4 Protection Against Physical Damage
- 11. 300.5 Underground Installations
- 12. 300.11(A)(2) Nonfire-Rated Ceiling Assemblies
- 13. 300.22 Wiring in Ducts and Other Spaces for Environmental Air (Plenums)
- 14. 310.15 Conductor Ampacity
- 15. 314.28(E) Power Distribution Block in Junction Box
- 16. 404.2(C) Switches Controlling Lighting
- 17. 406.4(D) Receptacle Replacements
- 18. 406.12 Tamper-Resistant Receptacles in Dwelling Units
- 19. 406.13 Tamper-Resistant Receptacles in Guest Rooms and Guest Suites
- 20. 406.14 Tamper-Resistant Receptacles in Child Care Facilities
- 21. 450.14 Disconnecting Means
- 22. 517.16 Receptacles with Insulated Grounding Terminal
- 23. 680.26 Equipotential Bonding
- 24. 680.73 Accessibility
- 25. 690.47 Grounding Electrode System
Top 25 changes to the 2011 National Electrical Code (NEC)
19. 406.13 Tamper-Resistant Receptacles in Guest Rooms and Guest Suites
A new requirement for tamper-resistant receptacles in guest rooms and guest suites was added.
406.13 Tamper-Resistant Receptacles in Guest Rooms and Guest Suites. Nonlocking-type 15A and 20A, 125V receptacles in guest rooms and guest suites must be listed as tamper-resistant.
Analysis: Guest rooms and guest suites often have children staying in them, so tamper-resistant receptacles have been added as a requirement for these locations. Guest suites that provide complete facilities for living, sleeping, cooking and sanitation are considered to be dwelling units by the NEC, and as such were already required to provide tamper-resistant receptacles. This change will now require tamper-resistant receptacles in all guest rooms and guest suites.