A new requirement for tamper-resistant receptacles in guest rooms and guest suites was added.

406.13 Tamper-Resistant Receptacles in Guest Rooms and Guest Suites. Nonlocking-type 15A and 20A, 125V receptacles in guest rooms and guest suites must be listed as tamper-resistant.

Analysis: Guest rooms and guest suites often have children staying in them, so tamper-resistant receptacles have been added as a requirement for these locations. Guest suites that provide complete facilities for living, sleeping, cooking and sanitation are considered to be dwelling units by the NEC, and as such were already required to provide tamper-resistant receptacles. This change will now require tamper-resistant receptacles in all guest rooms and guest suites.