2011 National Electrical Code Changes

1. 110.24 Available Fault Current

A new section requires some equipment to be marked with the available fault current and requires updating of that marking if modifications of the electrical system occur.

110.24 Available Fault Current.

(A) Field Marking. Service equipment in other than dwelling units must be legibly field-marked with the maximum available fault current, including the date the fault current calculation was performed and be of sufficient durability to withstand the environment involved. (click here to see Fig. 1)

(B) Modifications. When modifications to the electrical installation affect the maximum available fault current at the service, the maximum available fault current must be recalculated to ensure the service equipment ratings are sufficient for the maximum available fault current at the line terminals of the equipment. The required field marking(s) in 110.24(A) must be adjusted to reflect the new level of maximum available fault current.

Exception: Field markings aren’t required for industrial installations where conditions of maintenance and supervision ensure that only qualified persons service the equipment.

Analysis: All equipment must have an interrupting rating or short circuit current rating that’s equal to or greater than the available fault current [110.9 and 110.10]. As premises wiring systems age, utilities may change transformers in an effort to become more efficient or to increase capacity. When this occurs, the available fault current increases, many times resulting in noncompliant (and dangerous) wiring systems. This NEC change is intended to alert Code users to the fact that when utilities change transformers — or when emergency or standby systems are installed — the ratings of equipment must be re-evaluated.

Opponents of this NEC change argue that oftentimes the ratings of equipment are based on a “worst-case” scenario. While this is suitable for designing a system, it isn’t suitable for performing the calculations required to establish the proper personal protective equipment (PPE) necessary to work on the equipment. When artificially high values of fault current are used for equipment ratings, a lower PPE rating is often the result of the calculations.

Discuss this Article 18

Anonymous (not verified)
on Sep 3, 2012

Why change the isolated ground receptacle requirement?the hospitals here have been @ for 40 years now.why did it take so long for the code makers to figure that out? Tr receptacles r too expensive to install,that means people will not hire electricians to replace there receptacles.they will install the traditional type or just not install new ones.I feel imbarrased about being an electrician because of these code rules.

Anonymous (not verified)
on Sep 3, 2012

I think the worst code change is having to add ur own support. To secure wire above a ceiling grid.shouldn't. U also have to support the luminaire as well.in fact,why not just use the support wires that support the grid. Most of the code changes are a waste of time and money.

Anonymous (not verified)
on Oct 25, 2012

Apparently you dont understand!

Anonymous (not verified)
on Sep 3, 2012

I just want to know why it took so long for them to come up with this stuff.we went to the moon in 69 and now they just figured out how to support wire above a ceiling!

Anonymous (not verified)
on Oct 17, 2012

The UL listing for a device that draws current should be what demands the neutral, not the NEC. Hundreds of millions of ordinary switch loops should not have to be saddled with the cost of the relatively few that need a neutral

Anonymous (not verified)
on Oct 26, 2012

Changes for conduit is it true no more 1/2" conduit can b used.

Anonymous (not verified)
on Oct 31, 2012

Can anyone tell me what code sections are applicable to roof mounted solar systems. Just the changes from 08-2011. What changes will have to be made to roof solar systems per 2011 that weren't applicable in 2008

Anonymous (not verified)
on Nov 2, 2012

Is there a code requirement for using a GCFI for sump pumps and/or ejectors in basements? Also is it required for clothes washers?

Anonymous (not verified)
on Nov 8, 2012

I heard of a new code stating each and every circuit has to have its own neutral ? no more A,B,C, phase with one nuetral "full Boat"? is this true?

Anonymous (not verified)
on Apr 5, 2013

you can still network if using handle ties or three pole breaker

Anonymous (not verified)
on Nov 8, 2012

AFCI not work properly in over 50%

Anonymous (not verified)
on Feb 4, 2013

The fire safety code requires the use of our own grid wires. To make sure lights don't fall out of the ceiling onto the fire fighters head. Sucks but makes sense. If you install a breaker lock on the circuits so they can be switched off at the same time, so there isnt any unbalanced neutral loads so you can work the circuit safely. Again common sense. Most of the code is written to protect people other than electricians.

Anonymous (not verified)
on Feb 19, 2013

Sounds like most people calling themselves "electricians " should probably take a code class to "refresh" what they should already learned about in apprentice class.

Anthony, IAEI Member (not verified)
on Feb 25, 2013

Anyone can become involved in the code change process. There are multiple organizations you can join. Every year thousands of people work hard to try and make the code as good as it can get, and every year we realize it’s not perfect. If you do not try and make a difference you have no right to complain. If you really want to try and make a difference join a group and get involved. Everyone acts like they have no control over these changes. If you sit on the sidelines all your life and just watch you will never be anything more than a spectator!

Anonymous (not verified)
on Mar 14, 2013

Codes are there for a reason.If anyone could understand and apply them properly electricians wouldn't make the $ we make.

Anonymous (not verified)
on Mar 15, 2013

If a home sustained water damages to the electrical box and flooded basement and all floors does the National Code require that all wiring to the entier house be replaced?

Anonymous (not verified)
on Mar 22, 2013

Yes. Any electrical equipment that has been flooded should be replaced.

NEMA has a great document guide for evaluating flood damaged electrical equipment. Here is the link.
http://www.nema.org/Standards/ComplimentaryDocuments/Evaluating-Water-da...

Anonymous (not verified)
on Apr 11, 2013

when do have to change from t12 tubes to t 5 for ballast

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Apr. 15, 2013
video

Protection From Arc Flashes

Learn how arc flashes happen, how they are measured and how wearing the right flame resistant clothing can keep workers safe....More

Newsletter Signup

Connect With Us