2011 National Electrical Code Changes

15. 314.28(E) Power Distribution Block in Junction Box

New provisions for power distribution blocks in pull and junction boxes have been added.

314.28 Boxes and Conduit Bodies for Conductors 4 AWG and Larger.

(E) Power Distribution Block. Power distribution blocks installed in junction boxes over 100 cu in. must comply with the following (click here to see Fig. 15):

(1) Installation. Be listed as a power distribution block.

(2) Size. Be installed in a box not smaller than required by the installation instructions of the power distribution block.

(3) Wire-Bending Space. The junction box is sized so that the wire-bending space requirements of 312.6 can be met.

(4) Live Parts. Exposed live parts on the power distribution block aren’t present when the junction box cover is removed.

(5) Through Conductors. Where the junction box has conductors that don’t terminate on the power distribution block(s), the through conductors must be arranged so the power distribution block terminals are unobstructed following installation.

Analysis: Power distribution blocks have a history of being used in large pull and junction boxes despite the fact that the Code has been silent on these installations. The only requirements for power distribution blocks were found in Art. 376, which applies only to metal wireways. This left uncertainty regarding the installation requirements for these blocks in boxes. The NEC now addresses this practice and provides clear, concise rules.

Only boxes exceeding 100 cu. in. can contain these blocks, and they must be listed. The values in Table 312.6 can be used for bending space at the terminals, and live parts must be covered just as required for wireways.

Discuss this Article 18

Anonymous (not verified)
on Sep 3, 2012

Why change the isolated ground receptacle requirement?the hospitals here have been @ for 40 years now.why did it take so long for the code makers to figure that out? Tr receptacles r too expensive to install,that means people will not hire electricians to replace there receptacles.they will install the traditional type or just not install new ones.I feel imbarrased about being an electrician because of these code rules.

Anonymous (not verified)
on Sep 3, 2012

I think the worst code change is having to add ur own support. To secure wire above a ceiling grid.shouldn't. U also have to support the luminaire as well.in fact,why not just use the support wires that support the grid. Most of the code changes are a waste of time and money.

Anonymous (not verified)
on Oct 25, 2012

Apparently you dont understand!

Anonymous (not verified)
on Sep 3, 2012

I just want to know why it took so long for them to come up with this stuff.we went to the moon in 69 and now they just figured out how to support wire above a ceiling!

Anonymous (not verified)
on Oct 17, 2012

The UL listing for a device that draws current should be what demands the neutral, not the NEC. Hundreds of millions of ordinary switch loops should not have to be saddled with the cost of the relatively few that need a neutral

Anonymous (not verified)
on Oct 26, 2012

Changes for conduit is it true no more 1/2" conduit can b used.

Anonymous (not verified)
on Oct 31, 2012

Can anyone tell me what code sections are applicable to roof mounted solar systems. Just the changes from 08-2011. What changes will have to be made to roof solar systems per 2011 that weren't applicable in 2008

Anonymous (not verified)
on Nov 2, 2012

Is there a code requirement for using a GCFI for sump pumps and/or ejectors in basements? Also is it required for clothes washers?

Anonymous (not verified)
on Nov 8, 2012

I heard of a new code stating each and every circuit has to have its own neutral ? no more A,B,C, phase with one nuetral "full Boat"? is this true?

Anonymous (not verified)
on Apr 5, 2013

you can still network if using handle ties or three pole breaker

Anonymous (not verified)
on Nov 8, 2012

AFCI not work properly in over 50%

Anonymous (not verified)
on Feb 4, 2013

The fire safety code requires the use of our own grid wires. To make sure lights don't fall out of the ceiling onto the fire fighters head. Sucks but makes sense. If you install a breaker lock on the circuits so they can be switched off at the same time, so there isnt any unbalanced neutral loads so you can work the circuit safely. Again common sense. Most of the code is written to protect people other than electricians.

Anonymous (not verified)
on Feb 19, 2013

Sounds like most people calling themselves "electricians " should probably take a code class to "refresh" what they should already learned about in apprentice class.

Anthony, IAEI Member (not verified)
on Feb 25, 2013

Anyone can become involved in the code change process. There are multiple organizations you can join. Every year thousands of people work hard to try and make the code as good as it can get, and every year we realize it’s not perfect. If you do not try and make a difference you have no right to complain. If you really want to try and make a difference join a group and get involved. Everyone acts like they have no control over these changes. If you sit on the sidelines all your life and just watch you will never be anything more than a spectator!

Anonymous (not verified)
on Mar 14, 2013

Codes are there for a reason.If anyone could understand and apply them properly electricians wouldn't make the $ we make.

Anonymous (not verified)
on Mar 15, 2013

If a home sustained water damages to the electrical box and flooded basement and all floors does the National Code require that all wiring to the entier house be replaced?

Anonymous (not verified)
on Mar 22, 2013

Yes. Any electrical equipment that has been flooded should be replaced.

NEMA has a great document guide for evaluating flood damaged electrical equipment. Here is the link.
http://www.nema.org/Standards/ComplimentaryDocuments/Evaluating-Water-da...

Anonymous (not verified)
on Apr 11, 2013

when do have to change from t12 tubes to t 5 for ballast

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Nov. 24, 2008
video
Electrical Construction and Maintenance

Exterior Fixture Box for Brick or Stone

Installing a fixture box in a brick or stone wall just got easier with Arlington’s new adjustable depth box!...More

Newsletter Signup

Connect With Us