2011 National Electrical Code Changes

11. 300.5 Underground Installations

Type MI and Type MC Cables are now allowed to be installed under buildings without a raceway.

300.5(C) Cables Under Buildings. Cables installed under a building must be installed in a raceway that extends past the outside walls of the building.

Ex. 2: Type MC Cable listed for direct burial is permitted under a building without installation in a raceway [330.10(A)(5)]. (click here to see Fig. 10)

Analysis: Although certain types of MC cable are listed for direct burial and concrete encasement, this rule has prohibited them from being installed underneath buildings. This change now allows cables to be installed under the floor slab of a building, which has been accepted by many inspectors for some time. Interestingly, other cables that are listed for this application, such as UF cable, aren’t recognized by this change.

This change clarifies the use of single conductor cables installed in parallel.

300.5(I) Conductors Grouped Together. All conductors of the same circuit, including the equipment grounding conductor, must be inside the same raceway or in close proximity to each other. See 300.3(B).

Ex. 1: Conductors can be installed in parallel in raceways, multiconductor cables, or direct-buried single-conductor cables. Each raceway or multiconductor cable must contain all conductors of the same circuit, including the equipment grounding conductor. Each direct-buried single-conductor cable must be located in close proximity in the trench to the other single-conductor cables in the same parallel set of conductors, including equipment grounding conductors.

Ex. 2: Parallel circuit conductors installed in accordance with 310.10(H) of the same phase or neutral can be installed in underground PVC conduits, if inductive heating at raceway terminations is reduced by the use of aluminum locknuts and cutting a slot between the individual holes through which the conductors pass as required by 300.20(B).

Analysis: Conductors of the same circuit are required to be grouped in the same raceway or cable to help reduce the inductive reactance of the conductors. A very literal reading of previous Code editions didn’t address the use of single-conductor cables, such as many USE cables, in parallel installations. The NEC now recognizes this practice while giving guidance on how to install these cables. The issues of inductive reactance are addressed by requiring these single-conductor cables to be installed within close proximity of each other.

Discuss this Article 18

Anonymous (not verified)
on Sep 3, 2012

Why change the isolated ground receptacle requirement?the hospitals here have been @ for 40 years now.why did it take so long for the code makers to figure that out? Tr receptacles r too expensive to install,that means people will not hire electricians to replace there receptacles.they will install the traditional type or just not install new ones.I feel imbarrased about being an electrician because of these code rules.

Anonymous (not verified)
on Sep 3, 2012

I think the worst code change is having to add ur own support. To secure wire above a ceiling grid.shouldn't. U also have to support the luminaire as well.in fact,why not just use the support wires that support the grid. Most of the code changes are a waste of time and money.

Anonymous (not verified)
on Oct 25, 2012

Apparently you dont understand!

Anonymous (not verified)
on Sep 3, 2012

I just want to know why it took so long for them to come up with this stuff.we went to the moon in 69 and now they just figured out how to support wire above a ceiling!

Anonymous (not verified)
on Oct 17, 2012

The UL listing for a device that draws current should be what demands the neutral, not the NEC. Hundreds of millions of ordinary switch loops should not have to be saddled with the cost of the relatively few that need a neutral

Anonymous (not verified)
on Oct 26, 2012

Changes for conduit is it true no more 1/2" conduit can b used.

Anonymous (not verified)
on Oct 31, 2012

Can anyone tell me what code sections are applicable to roof mounted solar systems. Just the changes from 08-2011. What changes will have to be made to roof solar systems per 2011 that weren't applicable in 2008

Anonymous (not verified)
on Nov 2, 2012

Is there a code requirement for using a GCFI for sump pumps and/or ejectors in basements? Also is it required for clothes washers?

Anonymous (not verified)
on Nov 8, 2012

I heard of a new code stating each and every circuit has to have its own neutral ? no more A,B,C, phase with one nuetral "full Boat"? is this true?

Anonymous (not verified)
on Apr 5, 2013

you can still network if using handle ties or three pole breaker

Anonymous (not verified)
on Nov 8, 2012

AFCI not work properly in over 50%

Anonymous (not verified)
on Feb 4, 2013

The fire safety code requires the use of our own grid wires. To make sure lights don't fall out of the ceiling onto the fire fighters head. Sucks but makes sense. If you install a breaker lock on the circuits so they can be switched off at the same time, so there isnt any unbalanced neutral loads so you can work the circuit safely. Again common sense. Most of the code is written to protect people other than electricians.

Anonymous (not verified)
on Feb 19, 2013

Sounds like most people calling themselves "electricians " should probably take a code class to "refresh" what they should already learned about in apprentice class.

Anthony, IAEI Member (not verified)
on Feb 25, 2013

Anyone can become involved in the code change process. There are multiple organizations you can join. Every year thousands of people work hard to try and make the code as good as it can get, and every year we realize it’s not perfect. If you do not try and make a difference you have no right to complain. If you really want to try and make a difference join a group and get involved. Everyone acts like they have no control over these changes. If you sit on the sidelines all your life and just watch you will never be anything more than a spectator!

Anonymous (not verified)
on Mar 14, 2013

Codes are there for a reason.If anyone could understand and apply them properly electricians wouldn't make the $ we make.

Anonymous (not verified)
on Mar 15, 2013

If a home sustained water damages to the electrical box and flooded basement and all floors does the National Code require that all wiring to the entier house be replaced?

Anonymous (not verified)
on Mar 22, 2013

Yes. Any electrical equipment that has been flooded should be replaced.

NEMA has a great document guide for evaluating flood damaged electrical equipment. Here is the link.
http://www.nema.org/Standards/ComplimentaryDocuments/Evaluating-Water-da...

Anonymous (not verified)
on Apr 11, 2013

when do have to change from t12 tubes to t 5 for ballast

Post new comment
Sign In or register to use your Electrical Construction & Maintenance (EC&M) Magazine ID
(optional)

White Papers
EC&M Learning Center
Webinars
EC&M TV
Jan. 27, 2010
video
Electrical Construction and Maintenance

Arlington TV Box for Old Construction

Arlington’s recessed combination power and low voltage boxes – TV BOX™ and Indoor IN BOX™ – offer secure, convenient & easy way to mount LCD or plasma TVs flush against a wall....More

Newsletter Signup

Connect With Us