NEC in the Facility
Jan 4, 2010 4:36 PM
Retrofits, upgrades, and additions can result in a change to the "total load" used for sizing service conductors. Don't look only at the size of your service transformer(s) when adding equipment, upgrading HVAC, or making other configuration changes. Service conductors that were correctly sized with load diversification and other mitigating factors may suddenly be undersized.
Any time you add or change a load, you should recalculate the required ampacities of the conductors for the branch circuit, feeder, and service supplying that load. The service is the most critical, as loss of those conductors will shut down the whole area supplied by that service.
The ampacity of service conductors before any adjustment or correction factors must be at least the sum of the noncontinuous loads plus 125% of the continuous loads [230.42]. But if the service-entrance conductors terminate in an overcurrent protection device (and its assembly) listed for operation at 100% of rating, use the sum of noncontinuous and continuous loads.
Calculate each load per Art. 220, Part III, IV, or V as appropriate. Determine ampacity per 310.15.
Want to use this article? Click here for options!
© 2010 Penton Business Media, Inc.
MRO Insider
Safety
Mar 9, 2010 12:46 PM
The best protection against arc blast is "don’t be there." This, however, isn't always possible. The next best precaution is...
NEC in the Facility
Mar 9, 2010 12:43 PM
Most facilities today have surge arresters on the building supply (service). These are typically bought on a budget mentality that results in a waste of the entire investment. It doesn't have to be that way...
Failed Repairs
Mar 9, 2010 12:42 PM
A repair that isn't done correctly is a failure waiting to happen. Some common errors include...
Electrical Troubleshooting Quiz
Mar 9, 2010 12:27 PM
A rash of motor failures has afflicted your plant. Your plant engineer read some application notes from the Web site of a test instrument manufacturer and subsequently used a power analyzer on the feeders of these motors...
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
|
Whats Wrong Here?Mar 11, 2010 12:54 PM |
|
What's Wrong Here?Feb 18, 2010 5:04 PM |
|
What's Wrong Here?Feb 4, 2010 5:06 PM |
View all What's Wrong Here?
What's Wrong Here
Sponsored By:

Email