NEC in the Facility
Save money on intrinsically safe installations. How? Here are three ways:
- Use a general enclosure with intrinsically safe apparatus; permitted by 504.10(B).
- Rather than use special wiring methods, use any of the wiring methods suitable for unclassified locations when installing intrinsically safe apparatus [504.20].
- Don’t seal enclosures that contain only intrinsically safe apparatus (except as required by 501.15(F)(3)); permitted by [504.70].
- You must separate intrinsically safe conductors from nonintrinsically safe conductors [504.30(A)]. About half of Art. 504 is devoted to covering the details of how to do this.
- You must connect intrinsically safe apparatus, enclosures, and raceways (if metallic) to the equipment grounding conductor [504.50].
- Bond all metallic objects of an intrinsically safe system, per 250.100 [504.60].
- Ensure all intrinsically safe circuits are identified at terminal and junction locations in a manner that prevents unintentional interference with the circuits during testing and servicing [504.80].
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
EV charger tester
May 25, 2012 8:26 AM
CFL/LED dimmer
May 24, 2012 8:48 AM
Load bank
May 23, 2012 9:33 AM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.